Emerson MPR15 Series User Manual

Page of 120
Installation and start-up procedures   59 
25A Switch Mode Rectifier
NT5C06B / C   Installation and User Manual
 
LVD installation in the shelf 
The LVD is installed in the right hand shelf position as describes in 
Procedure 10. 
Procedure 10 - LVD installation in the shelf 
Step Action 
Release the clamping bar and blank panel (see Procedure 1). 
Remove the LVD faceplate. 
Slide the LVD about two thirds of the way into the shelf. 
Connect the LVD as shown in Figure 22 and 23. (Use 2 X 10 AWG wires 
for contactors). 
Re-install the small LVD faceplate. 
Push the LVD the remaining distance into the shelf and slide the blank 
panel into the shelf between the LVD and the adjacent rectifier. 
Secure the clamping bar by tightening the two captive screws. 
end
 
Figure 22 - Embedded shelf - LVD connections - rear access 
2
1
8
CHASSIS
GROUND
BAT SENSE
LEADS
TO LOAD
[T]
[B]
BAT 
LOAD
BAT RTN