60   Installation and start-up procedures 
UM5C06B / C ( 169-2071-500 )   P0711722   Standard 10.00   May 2001 
Figure 23 - Embedded shelf - LVD connections - side access 
Start-up procedure 
Factory set voltage limits 
All rectifiers are factory set as follows unless otherwise requested by the 
customer: 
MPR15 MPR25 
Float Voltage: 
52.10 V DC 
48.00 V DC 
Equalize: 
  0.70 V DC above float    0.00 V DC above float 
HVSD: 
59.00 V DC 
56.50 V DC 
LVD/LVD Alarms 
Low Voltage Alarm (LVA): 
47.00 V DC 
Low Voltage Disconnect (LVD): 
43.50 V DC 