74   Maintenance 
UM5C06B / C ( 169-2071-500 )   P0711722   Standard 10.00   May 2001 
Filter 
If the unit operates in a dusty environment the optional fan filter is 
recommended.  It must be inspected and replaced, or thoroughly cleaned, at 
least every 12 months. 
 
 
 
 
CAUTION 
Do not install a wet filter in the unit.
 
To remove the filter, simply unscrew it. Re-install it by reversing the 
operation. 
Fan cooling 
Visually inspect the intake of the airflow for any obstruction by foreign 
objects or excessive dust and dirt build-up. Open both the DC and AC 
breakers (toggle them to OFF) and remove the unit from the power shelf. 
Inspect the air outlet for obstruction by foreign objects. Visually inspect the 
air outlet of the enclosure or cabinet. If a problem is detected in the rectifier, 
contact your local Astec service facility. The unit must not be opened for on-
site servicing. 
 
 
 
DANGER 
Do not attempt to access the inside of the unit with a 
tool or finger. Severe electrical shock could result.
 
Storage 
The rectifier contains aluminum electrolytic capacitors. For this reason, the 
rectifier must be in operation. If not in operation, once a year, the equipment 
must be energized for at least two hours to maintain the electrolytic 
capacitors in working condition. 
Power shelf 
The rectifier shelf requires no maintenance.