76   Maintenance 
UM5C06B / C ( 169-2071-500 )   P0711722   Standard 10.00   May 2001 
Load sharing 
Verify that the sense leads of all the rectifiers are connected to a common 
point (across the battery or output power terminals of the power shelf, or at 
the discharge busbar). 
Readjust the rectifier’s float voltage until all the rectifiers share the load. It is 
recommended that the current from each rectifier be 3 amperes minimum 
for best results. 
It is also recommended to leave the units functioning for at least 30 minutes 
to reach full stability, prior to final system adjustment. 
Fan failure 
Fan failure is indicated by the absence of fan rotation. The rectifier will be 
inhibited and an RFA and Fan alarm will be activated. The Fan Fail LED will 
turn RED. 
Fan replacement procedure 
 
 
DANGER 
Before replacing the fan, turn the rectifier off. Remove the 
rectifier from the shelf. Wait five minutes to allow all 
internal capacitors to fully discharge.
 
 
  
  
  
CAUTION 
Take the necessary precautions to prevent any dirt, dust, 
moisture, or metallic particles from falling into the unit.
 
Procedure 21 - Fan replacement 
Step Action 
With the unit sitting solidly on a clean workbench, carefully remove the 
five mounting screws that secure the fan assembly (see Figure 27). 
Slowly and carefully remove the fan assembly by pulling it from the 
chassis. 
Take note of which side the wire is connected to the fan and disconnect 
the fan connector (three pins). 
continued