4.4.2 
Off-delay 
Short description 
When an on-delay is set, the output is reset when the configured time has expired.    
 
Symbol in LOGO! 
Wiring 
Description 
Input Trg 
The off-delay timer starts with a negative edge (1 to 0 
transition) at input Trg (Trigger) 
Input R 
A signal at input R resets the on-delay time and the 
output. 
Parameter 
The output switches off (transitions from1 to 0) when 
the delay time T expires. 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
4
7UJ
5
3DU
 
Output Q 
Q is set with a signal at input Trg. It holds this state 
until T has expired. 
Parameter T 
Note the parameter T defaults specified in topic Time response (Page 151). 
The time for parameter T can be based on the actual value of another, already-configured 
function. You can use the actual value of the following functions:  
●  Analog comparator (Page 218) (actual value Ax - Ay) 
●  Analog threshold trigger (Page 213) (actual value Ax) 
●  Analog amplifier (Pag226) (actual value Ax) 
●  Analog multiplexer (Page 248) (actual value AQ) 
●  Analog Ramp (Page 251) (actual value AQ) 
●  Mathematic instruction (Page 265) (actual value AQ) 
●  PI controller (Page 256) (actual value AQ) 
●  Up/down counter (Pag201) (actual value Cnt) 
 
If your LOGO! is a LOGO! 0BA7, you can additionally use the actual values of the following 
functions: 
●  Analog filter (0BA7 only) (Page 271) (actual value AQ) 
●  Average value (0BA7 only) (Page 276) (0BA7 only) (actual value AQ) 
●  Max/Min (0BA7 only) (Page 273) (0BA7 only) (actual value AQ) 
●  On-delay (Page 160) (current time Ta) 
●  Off-delay (current time Ta) 
●  On-/Off-delay (Page 166) (current time Ta)