LOGO! installation and wiring 
 
2.1 Modular LOGO! setup 
 
LOGO! 
32
 
Manual, 04/2011, A5E03556174-01 
2.1 
Modular LOGO! setup 
2.1.1 
Maximum LOGO! network setup (0BA7 only) 
Maximum LOGO! 0BA7 network setup 
LOGO! 0BA7 supports SIMATIC S7 communication via 10/100 Mbit/s TCP/IP Ethernet.  
A LOGO! 0BA7 device can support a maximum of 8+1 network connections as described 
below: 
●  8: A maximum of eight TCP/IP-based S7 communication connections with the following 
devices: 
–  Additional LOGO! 0BA7 devices 
–  SIMATIC S7 PLCs with Ethernet functionality 
–  A maximum of one SIMATIC HMI that supports Ethernet communication with 
networked S7 PLCs 
●  1: A maximum of one TCP/IP Ethernet connection between a LOGO! Base Module and a 
PC with LOGO!Soft Comfort V7.0 installed 
 
 
Note 
You can only construct a LOGO! 0BA7 network topology using LOGO!Soft Comfort V7.0.