Siemens 6ED1050-1AA00-0BE8 User Manual
Technical data
A.5 Technical data: LOGO! DM8 24 and LOGO! DM16 24
LOGO!
328
Manual, 04/2011, A5E03556174-01
LOGO! 24
LOGO! 24o
LOGO! 24o
LOGO! 24C
LOGO! 24Co
LOGO! 24Co
Ohmic load/lamp load
10 Hz
10 Hz
Inductive load
0.5 Hz
0.5 Hz
1)
When LOGO! 24/24o, LOGO! 24C/24Co, LOGO! DM8 24 or LOGO! DM16 24 are switched on,
signal 1 is sent to the digital outputs for about 50 μs. Take this into account, especially when using
devices that react to short pulses.
devices that react to short pulses.
2)
The maximum switching rate is only dependent on the switching program's cycle time.
A.5
Technical data: LOGO! DM8 24 and LOGO! DM16 24
LOGO! DM8 24
LOGO! DM16 24
Power supply
Input voltage
Input voltage
24 V DC
24 V DC
Permissible range
20.4 ... 28.8 V DC
20.4 ... 28.8 V DC
Reverse polarity protection
Yes
Yes
Permissible mains frequency
- -
- -
Power consumption from 24 V
DC
30 ... 45 mA
0.3 A per output
0.3 A per output
30 ... 45 mA
0.3 A per output
0.3 A per output
Power loss at 24 V
0.8 ... 1.1 W
0.8 ... 1.7 W
Digital inputs
Number
Number
4
8
Electrical isolation
No
No
Number of high speed inputs
0
0
Input frequency
•
•
Normal input
•
High speed input
•
max. 4 Hz
•
- -
•
max. 4 Hz
•
- -
Max. continuous permissible
voltage
28.8 V DC
28.8 V DC
Input voltage
•
•
Signal 0
•
Signal 1
L+
•
•
< 5 V DC
•
> 12 V DC
L+
•
•
< 5 V DC
•
> 12 V DC
Input current at
•
•
Signal 0
•
Signal 1
•
< 0.85 mA
•
> 2 mA
•
< 0.85 mA
•
> 2 mA
Delay time at
•
•
0 to 1
•
1 to 0
•
typ. 1.5 ms
•
typ. 1.5 ms
•
typ. 1.5 ms
•
typ. 1.5 ms
Line length (unshielded)
max. 100 m
max. 100 m
Digital outputs