Siemens 6ED1050-1AA00-0BE8 User Manual

Page of 372
Technical data 
 
A.5 Technical data: LOGO! DM8 24 and LOGO! DM16 24 
 
LOGO! 
328
 
Manual, 04/2011, A5E03556174-01 
 
LOGO! 24 
LOGO! 24o 
LOGO! 24C 
LOGO! 24Co 
Ohmic load/lamp load 
10 Hz 
10 Hz 
Inductive load 
0.5 Hz 
0.5 Hz 
1)
  When LOGO! 24/24o, LOGO! 24C/24Co, LOGO! DM8 24 or LOGO! DM16 24 are switched on, 
signal 1 is sent to the digital outputs for about 50 μs. Take this into account, especially when using 
devices that react to short pulses. 
2)
  The maximum switching rate is only dependent on the switching program's cycle time.  
A.5 
Technical data: LOGO! DM8 24 and LOGO! DM16 24 
 
 
LOGO! DM8 24 
LOGO! DM16 24 
Power supply 
Input voltage 
24 V DC 
24 V DC 
Permissible range 
20.4 ... 28.8 V DC 
20.4 ... 28.8 V DC 
Reverse polarity protection 
Yes 
Yes 
Permissible mains frequency 
- - 
- - 
Power consumption from 24 V 
DC 
30 ... 45 mA 
0.3 A per output 
30 ... 45 mA 
0.3 A per output 
Power loss at 24 V 
0.8 ... 1.1 W 
0.8 ... 1.7 W 
Digital inputs 
Number 
Electrical isolation 
No 
No 
Number of high speed inputs 
Input frequency 
• 
Normal input 
• 
High speed input 
 
• 
max. 4 Hz 
• 
- - 
 
• 
max. 4 Hz 
• 
- - 
Max. continuous permissible 
voltage 
28.8 V DC 
28.8 V DC 
Input voltage  
• 
Signal 0 
• 
Signal 1 
L+ 
• 
< 5 V DC 
• 
> 12 V DC 
L+ 
• 
< 5 V DC 
• 
> 12 V DC 
Input current at 
• 
Signal 0 
• 
Signal 1 
 
• 
< 0.85 mA 
• 
> 2 mA 
 
• 
< 0.85 mA 
• 
> 2 mA 
Delay time at  
• 
0 to 1 
• 
1 to 0 
 
• 
typ. 1.5 ms 
• 
typ. 1.5 ms 
 
• 
typ. 1.5 ms 
• 
typ. 1.5 ms 
Line length (unshielded) 
max. 100 m 
max. 100 m 
Digital outputs