Siemens X-400 User Manual

Page of 148
Installation and Commissioning 
 
Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches 
90 
C79000-G8976-C186-03 
6.6 Ports 
6.6.1  Power Supply Connectors (X1) 
Polarity Reversal Protection X1, X2 
The two 4-pin male connectors (X1, X2) for the power supply and the signaling 
contact have no polarity reversal protection. If the connectors are accidentally 
swapped over, this does not cause damage or destroy circuits. Normal functionality 
is, however, not available while the connectors are swapped over. 
The redundant power supply is connected over a 4-pin connector at the front ter-
minal block on the power module. 
 
X 2
X 1
L 2
M 2
M 1
L 1
Figure 6-9 
Pin assignment of connector X1 
 
Conn. 1 
L1+ 
+ 24 V power supply 1 
 M1 
Ground 
 M2 
Ground 
 
L2+ 
+ 24 V power supply 2