Generac HTSN400K3 Leaflet
HTS 100-400 Amp
INTERCONNECTIONS
Switches and Indicators:
• System Ready LED
• Standby Operating LED
• Switch Position LED’s
• Utility Available LED
• Test Switch
• Fast Test Switch
• Return to Normal Switch
• Safety Disconnect Switch
Standby Accept Voltage ...............................................................................................................................................................................85-95%
Standby Accept Frequency ..........................................................................................................................................................................85-95%
Nominal Voltage............................................................................................................................................................................ 1 Volt Increments
Allowable Deviation of Utility ........................................................................................................................................................................1-100%
Line Interruption Delay .......................................................................................................................................................................1-10 Seconds
Engine Warmup Time .......................................................................................................................................................................1-300 Seconds
Minimum Run Time ............................................................................................................................................................................. 5-60 Minutes
Return to Utility Timer .......................................................................................................................................................................... 1-30 Minutes
Engine Cooldown Timer ...................................................................................................................................................................... 1-30 Minutes
Signal Before Transfer Timer ..............................................................................................................................................................1-30 Seconds
Transfer Type ................................................................................................................................................................Inphase Time Delay Neutral
Phase Difference for Inphase Transfer ............................................................................................................................................. -7 +0 Degrees
Standby Accept Frequency ..........................................................................................................................................................................85-95%
Nominal Voltage............................................................................................................................................................................ 1 Volt Increments
Allowable Deviation of Utility ........................................................................................................................................................................1-100%
Line Interruption Delay .......................................................................................................................................................................1-10 Seconds
Engine Warmup Time .......................................................................................................................................................................1-300 Seconds
Minimum Run Time ............................................................................................................................................................................. 5-60 Minutes
Return to Utility Timer .......................................................................................................................................................................... 1-30 Minutes
Engine Cooldown Timer ...................................................................................................................................................................... 1-30 Minutes
Signal Before Transfer Timer ..............................................................................................................................................................1-30 Seconds
Transfer Type ................................................................................................................................................................Inphase Time Delay Neutral
Phase Difference for Inphase Transfer ............................................................................................................................................. -7 +0 Degrees
WITHSTAND CURRENT – 600 VOLT HTS SERIES
HTS RATED AMPS
100
150
200
300
400
FUSE PROTECTED
Maximum RMS Symmetrical
Faul Current – Amps
200,000
200,000
200,000
200,000
200,000
Maximum Fuse Size – Amps
200
400
400
600
600
Fuse Class
J,T
J,T
J,T
J,T
J,T
CIRCUIT BREAKER PROTECTED
Maximum RMS Symmetrical
Fault Current – Amps
Maximum RMS Symmetrical
Fault Current – Amps
14,000
25,000
25,000
35,000
35,000
Protective Device Continuous
Rating (Max.) – Amps
Rating (Max.) – Amps
150
300
300
600
600
• Tested in accordance with the withstand and closing requirements of UL 1008 and CSA Standards.
• Current ratings are listed @ 480 VAC.
• Current ratings are listed @ 480 VAC.
UNIT DIMENSIONS
HTS
VOLTAGE
ENCLOSURE
ENCLOSURE
WALL MOUNT
ENCLOSURE WEIGHT
RATED
HEIGHT
WIDTH
BOLT PATTERN
DEPTH
(lbs.)
AMPS
H
W
M1
M2
D1
D2
100
ALL
36
24
18
37.5
12.7
10
180
150-200
120/240
36
24
18
37.5
12.7
10
185
150-200
120/208
36
24
18
37.5
12.7
10
185
150-200
277/480
48*
30*
24
49.5
14.8
12
265
300-400
120/240
36
24
18
37.5
12.7
10
245
300-400
120/208
36
24
18
37.5
12.7
10
245
300-400
277/480
48*
30*
24
49.5
14.8
12
325
HTS RATED
CONTACTOR TERMINALS
(1 LUG PER POLE)
NEUTRAL BAR*
GROUND LUG
(1 PROVIDED)
AMPS
LUG WIRE RANGE
# LUGS
LUG WIRE RANGE
LUG WIRE RANGE
100
2/0 – 14 AWG
4
2/0 – 14 AWG
2/0 – 14 AWG
150
400MCM – 4 AWG
4
350MCM – 6 AWG
350MCM – 6 AWG
200
400MCM – 4 AWG
4
350MCM – 6 AWG
350MCM – 6 AWG
300
600MCM – 4 AWG
4
600MCM – 4 AWG
350MCM – 6 AWG
or 2 – [250MCM – 1/0 AWG]
[250MCM – 1/0 AWG]**
350MCM – 6 AWG
400
600MCM – 4 AWG
4
600MCM – 4 AWG
350MCM – 6 AWG
or 2 – [250MCM – 1/0 AWG]
[250MCM – 1/0 AWG]**
TERMINAL LUG WIRE RANGES
* Not included in HTS with switched neutral. ** Allowable wire range in brackets is for 2 wires per lug.