Generac HTSN400K3 Leaflet

Page of 2
HTS 100-400 Amp
INTERCONNECTIONS
Switches and Indicators:
•  System Ready LED
•  Standby Operating LED
•  Switch Position LED’s
•  Utility Available LED
•  Test Switch
•  Fast Test Switch
•  Return to Normal Switch
•  Safety Disconnect Switch
Standby Accept Voltage ...............................................................................................................................................................................85-95%
Standby Accept Frequency ..........................................................................................................................................................................85-95%
Nominal Voltage............................................................................................................................................................................ 1 Volt Increments
Allowable Deviation of Utility ........................................................................................................................................................................1-100%
Line Interruption Delay .......................................................................................................................................................................1-10 Seconds
Engine Warmup Time .......................................................................................................................................................................1-300 Seconds
Minimum Run Time ............................................................................................................................................................................. 5-60 Minutes
Return to Utility Timer .......................................................................................................................................................................... 1-30 Minutes
Engine Cooldown Timer ...................................................................................................................................................................... 1-30 Minutes
Signal Before Transfer Timer ..............................................................................................................................................................1-30 Seconds
Transfer Type ................................................................................................................................................................Inphase Time Delay Neutral
Phase Difference for Inphase Transfer .............................................................................................................................................  -7 +0 Degrees
WITHSTAND CURRENT – 600 VOLT HTS SERIES
HTS RATED AMPS 
100 
150 
200 
300 
400
FUSE PROTECTED
Maximum RMS Symmetrical
  Faul Current – Amps
200,000
200,000
200,000
200,000
200,000
 Maximum Fuse Size – Amps
200
400
400
600
600
 Fuse Class
J,T
J,T
J,T
J,T
J,T
CIRCUIT BREAKER PROTECTED
 Maximum RMS Symmetrical
  Fault Current – Amps
14,000
25,000
25,000
35,000
35,000
 Protective Device Continuous
  Rating (Max.) – Amps
150
300
300
600
600
 • Tested in accordance with the withstand and closing requirements of UL 1008 and CSA Standards.
 • Current ratings are listed @ 480 VAC.
UNIT DIMENSIONS
  HTS 
VOLTAGE 
ENCLOSURE 
ENCLOSURE 
WALL MOUNT 
ENCLOSURE  WEIGHT
  RATED 
 
HEIGHT 
WIDTH 
BOLT PATTERN 
DEPTH 
(lbs.)
  AMPS 
 
M1 
M2 
D1 
D2
 100
ALL
36
24
18
37.5
12.7
10
180
150-200
120/240
36
24
18
37.5
12.7
10
185
150-200
120/208
36
24
18
37.5
12.7
10
185
150-200
277/480
48*
30*
24
49.5
14.8
12
265
300-400
120/240
36
24
18
37.5
12.7
10
245
300-400
120/208
36
24
18
37.5
12.7
10
245
300-400
277/480
48*
30*
24
49.5
14.8
12
325
  HTS RATED 
CONTACTOR TERMINALS
(1 LUG PER POLE)
NEUTRAL BAR* 
GROUND LUG 
(1 PROVIDED)
AMPS 
LUG WIRE RANGE 
# LUGS 
LUG WIRE RANGE 
LUG WIRE RANGE
100
2/0 – 14 AWG
4
2/0 – 14 AWG
2/0 – 14 AWG
150
400MCM – 4 AWG
4
350MCM – 6 AWG
350MCM – 6 AWG
200
400MCM – 4 AWG
4
350MCM – 6 AWG
350MCM – 6 AWG
300
600MCM – 4 AWG
4
600MCM – 4 AWG
350MCM – 6 AWG
or 2 – [250MCM – 1/0 AWG]
[250MCM – 1/0 AWG]**
350MCM – 6 AWG
400
600MCM – 4 AWG
4
600MCM – 4 AWG
350MCM – 6 AWG
or 2 – [250MCM – 1/0 AWG]
[250MCM – 1/0 AWG]**
TERMINAL LUG WIRE RANGES
* Not included in HTS with switched neutral. ** Allowable wire range in brackets is for 2 wires per lug.