Fujitsu C122-H007-01EN User Manual

Page of 58
CHAPTER 2 Connected Information 
2.5 Free Access Underfloor Connection of Power Cable 
31 
C122-H007-01EN 
 
2.4.3  Power Distribution Box and Distribution Panel 
Following table shows the power supply cable specifications of power distribution box and distribution panel. 
TABLE 2.4 Power Supply Cable Specifications of Power Distribution Box and Distribution Panel 
Destination 
Plug format 
Remarks 
200V for countries 
other than Japan 
NEMAL6-30P 
Recipient power 
distribution format  
 
NEMA L6-30R (30A-
220V) 
200V for Brazil 
IEC60309-32A 
Recipient power 
distribution format  
 
IEC60309-32A (32A-
250V) 
Remarks 
Power cable supplied with the device and power cord supplied with the option part, are not used for the 
power cable which is connected to the device. However, the supplied power cable is not used for the other 
products. 
2.5 
Free Access Underfloor Connection of Power Cable 
If the height of underfloor is less than 300mm (11.8 in.), the power distribution is set to sideways. 
FIGURE 2.26 When Underfloor Height is less than 300mm (11.8 in) 
 
 
Number 
Description 
(1) 
Free access floor 
(2) 
Less than 300mm (11.8 in) 
(3) 
Recipient power distribution  
 
The connector format and cable bend radius of power cable are considered at the time of connecting the 
power cable of power distribution box (or base cabinet, PCI_Box) under the free access floor. It is 
recommended that the under floor height is 300 mm (11.8 in) or more. 
The recipient power distribution should be arranged near the device. 
FIGURE 2.27 When the under floor height is 300 mm (11.8 in) or more.