DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r  
555-233-115  
Issue 1
April 2000
Multicarrier G2 Universal Module to R8r EPN 
5-6
Read This First 
5
Alarm Connection
The D6 connector on G2 systems had 31 alarm-monitor appearances (Unit 1 to 
Unit 31) for external equipment. The AUXILIARY connector on an R8 PPN only 
has appearances for 1M (major alarm) and 1m (minor alarm). If the G2 system 
being upgraded used more than 1 major or more than 1 minor alarm-monitor 
appearance, these extra appearances, they can either be distributed to the 
AUXILIARY connector on a DEFINITY ECS Release 8 EPN, or “ganged” so that 
several external devices share the same appearance. The alarms can also be 
accommodated by paralleling them to the above connections.
NOTE:
When several external devices are ganged to the same appearance, each 
device loses its individual identity. An alarm on a shared appearance only 
denotes that 1 of several devices reported a problem. Subsequent 
maintenance effort is needed to determine which device reported the 
problem and the nature of the problem.
The control circuit pack behind the AUXILIARY connector detects external 
alarms with a ground-detector chip. Therefore, to gang several external 
devices, every device must be able to return a true relay ground closure to 
the AUXILIARY connector. Alternatives, such as a TTL low driver, are 
inadequate.
The following tables correlate wall-field terminal numbers, connector pin 
numbers, lead colors, and lead designations for the G2 D6 and DEFINITY ECS 
Release 8 AUXILIARY connectors.