Lucent Technologies 555-233-115 User Manual
DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r
Upgrades and Additions for R8r
555-233-115
Issue 1
April 2000
Upgrading G3rV2, V3, V4 to R8r and Adding Memory
1-15
Upgrade the software and hardware
1
Verify Interchange (H/C only)
This step is performed twice, once for each carrier but not at the same time.
NOTE:
Because of the memory mismatch between the standby and active SPEs,
typing the status spe command yields two different scenarios.
typing the status spe command yields two different scenarios.
After the circuit packs have been replaced in the first carrier:
1. Type status spe and press
Enter:
■
The
Standby Refreshed
field shows no
■
The
Standby Shadowing
field shows off
■
The
Standby Handshake
field shows up
After the circuit packs have been replaced in the second carrier:
1. Type status spe and press
Enter
to make sure the active side is ready for
interchange. When it is ready,
■
The
Standby Refreshed
field shows yes
■
The
Standby Shadowing
field shows on
■
The
Standby Handshake
field shows up
Upgrade other carrier (H/C only)
To upgrade the other carrier, lock the SPE switches on the DUPINT to the other
carrier.
carrier.
NOTE:
The new active carrier resets (cold 2 restart). Wait until the login prompt
appears then log in.
appears then log in.
Repeat the steps from
Affix position label(s)
1. Place the new strip label(s) over the old carrier label(s).