Siemens TPS3 12 User Manual

Page of 16
PRE-PLAN INSTALLATION TO ACCOMPLISH THE FOLLOWING:
Meet all National and Local codes (NEC® Article 285 addresses
SPDs)
Mount SPD as close to panel or equipment as possible to keep
leads short
Ensure  leads  are  as  short  and  straight  as  possible,  including
neutral and ground. Consider a breaker position that is closest
to the SPD and the panel’s neutral & ground
Suggested breaker & conductor size is 60A-30A with 6 AWG
Make sure system is grounded per NEC® and clear of faults before
energizing SPD.
CERTAIN  OPTIONS  OR  IMPLEMENTATIONS  REQUIRE  EXTRA
CONSIDERATION.  SEE  APPROPRIATE  SECTIONS  WITHIN  THIS
MANUAL:
Line Side Installation (page 4)
Disconnect Switch Option (page 9)
Flush Mount Option (page 9)
Retro-fit where no breaker positions are available (page 9)
NEMA 3R drain holes (page 7)
TPS3 12 and TPS3 15 Installation Instructions
CONDUCtING DIeLeCtRIC AND/OR 
HI-pOteNtIAL teStING WILL CAUSe
INteRNAL DAMAGe tO tpS3 UNIt.
Do not perform dielectric or high potential 
tests with the TPS3 unit installed.
CAUtION
V
Hazardous voltage.
Will cause death or serious injury.
Keep Out.
Qualified personnel only.
Disconnect and lock off all power before 
working on this equipment.
V  
DANGER
Use a voltmeter to check all voltages to ensure correct SPD
If  SPD  has  Dry  Contact,  Remote  Monitoring  or  Remote  Display,
pre-plan their installation
Remove power for panel. Confirm panel is deenergized.
Identify connection/breaker location and SPD location.
Make sure leads are short. Reducing inches matters.
Installation Tips: SPD module is mounted on backplane within
its enclosure. In many cases, the backplane assembly can be
unbolted and rotated in two or four directions to yield shortest
leads. See Figure 7. Carefully disconnect ribbon cable(s) and
unbolt  backplane  assembly.  Various  configurations  have
limited work space. Please be patient. Installation may be
easier if disconnect switch is temporarily removed from DIN-
rail, or module/backplane is temporarily removed.
Remove  an  appropriately  sized  knockout  from  panel.  Create  an
appropriately sized and located hole in the SPD enclosure.
Mount SPD. Connect to equipment using an approved wiring method,
including seals appropriate for the enclosure rating. Carefully reinstall
backplane or disconnect switch as appropriate.
Connect conductors as appropriate – short and straight as possible
(Note that Hi-Legs are Phase B)
Label  or  mark  conductors  as  appropriate  (neutral:  white,  ground:
green, energized: black, hi-leg: orange)
Make sure system is bonded per NEC® and is clear of hazards or faults
before energizing (N-G bonding not per NEC® will fail SPDs: #1 cause
of SPD failures)
Energize and confirm proper operation of indicators and/or options.
Figure 3: Panel Installation
A
B
C
G
N
BREAKER
Use closest breaker to SPD
Locate SPD close to intended
breaker
Keep Leads Short as Possible
Avoid Sharp Bends
Outdoor installation requires
appropriate weather sealing at nipple
(o-ring, sealing condulet, etc.)
To Protected Loads
8