2008 Nec Art 285 & ul 1449-3
SPD Types: Types 1, 2, 3, & 4
Based on Location within electrical distribution system
(also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B &A)
Figure 1: SPD Types
General Information
Product Family Outline
TPS3 12 – Single Module in enclosure
TPS3 15 – Two Modules in enclosure
Each is available with Standard modes (most common) or discrete
10-modes (specific application). For example, TPS3 12 is a SPD in an
enclosure with Standard modes of protection; TPS3 L12 is a SPD with
an enclosure having discrete ten mode protection.
The TPS3 12 & TPS3 15 families are intended for use as a Type 1 external
mount SPD. See Model Number Decoder in Table 1 (page 3).
Type 1 SPD
Type 1 SPDs include internal overcurrent protection and have been
evaluated  by  UL  to  more  stringent  requirements.  Type  1  SPDs  are
suitable for installation on the line side or load side of the service
disconnect overcurrent device. Type 1 SPDs may be used in Type 2
applications.
Internal Protection
This  device  features  internal  overcurrent  and  overtemperature
protection that will disconnect effected surge suppression components
at the end of their useful life, but will maintain power to the load –
now unprotected. If this situation is undesirable for the application,
follow these instructions for servicing or replacing the device.
Service Guidelines
Service  of  this  unit  consists  of  replacing  the  internal  module(s),
disconnect switch (if equipped) and/or display assembly.
There are no user-serviceable parts inside the replaceable module.
Do not attempt to disassemble the module as it stores charge.
Simplified Explanation of Operation
As SPDs sense overvoltage, they create a momentary internal short
circuit, thereby redirecting harmful surge energy to earth ground.
SPDs are capable of repeating this function repeatedly. For optimum
protection, staged surge suppression should be implemented at the
service entrance and all other distribution or panelboard locations
feeding sensitive equipment.
Industry Standards Changes - 2009
UL 1449 Third Edition and 2008 NEC® Article 285 generated substantial
changes.
The term TVSS changed to SPD
Types 1, 2, 3 & 4 SPDs are created
UL 1449 clamping voltage performance testing changed from
500A to 3,000A
UL 1449 added new Nominal Discharge Current testing (I nominal,
or In), which consists of more rigorous duty-cycle testing
The SPD Type category is important to understand before installing
any SPD. Type 1 and 2 SPDs are fully UL Listed devices whereas Type
4 SPDs are UL Recognized devices.
Type  1  –  Installed  on  line  or  load  side  of  the  Main  Overcurrent
Protection (OCP), similar to obsolete products known as Secondary
Surge Arrestors, except now includes rigorous safety testing. Includes
all OCP & safety disconnectors inside the SPD.
Type 2 – Installed on load side of the Main OCP, similar to previous
products known as TVSS. May or may not require external OCP.
Type 3 – Point of Utilization, direct plug in type devices, surge strips,
etc. Theses devices are intended for installation 10 meters from the
panel (rationale based on IEEE Cat. A location).
Type 4 – Surge suppression components, could be a basic component
or a complete module. Type 4 components can be tested for Type 1,
Type 2 or Type 3 applications.