APC Symmetra LX 8kVA UPS SYA8K16PXR User Manual

Product codes
SYA8K16PXR
Page of 25
C
HAPTER 
2:
  
B
ASIC 
C
OMMANDS
 
 5  
5.  In approximately 90 seconds, the green Load On indicator will illuminate and this message will appear. 
 
UPS LOAD IS ON 
Press any key… 
 
Turn Off UPS Output Power and Load Equipment 
1.  Press ‘Esc’ until the Main Menu appears.  
>Control      Logging 
Status        Display 
Setup         Diags 
Accessories   Help 
2.  Scroll down and select the ‘Turn UPS Output Off’ command. 
Graceful Turn Off 
Start Runtime Cal 
>Turn UPS Output Off 
 
3.  Confirm choice by selecting ‘YES’.  
Confirm: 
     Turn UPS Off 
  NO, ABORT 
     >YES, Turn UPS OFF 
You will hear some clicking sounds and see the following message. 
UPS HAS BEEN 
COMMANDED TO TURN 
LOAD POWER OFF 
 
In approximately 90 seconds, you will see the following message and the green Load On status indicator will 
be OFF. 
The output is now off. 
 
UPS LOAD IS OFF 
 
   Press any key…  
4.  To fully remove power from the UPS, turn OFF the system enable switch, and open the input circuit breaker. 
Bypass Operation 
The bypass operation can be performed manually, using the maintenance bypass switch, or automatically, using 
the PowerView to issue commands. 
 
•  In either bypass mode, the utility and circuit breakers must be turned on. 
•  The UPS must remain functional to stay in command bypass mode. Put the UPS in maintenance 
bypass before turning off the system enable switch, or removing both intelligence modules.