Cal Flame Spa Wrap User Manual

Page of 16
2009 Spa Wraps
LTR20091032, Rev. A
Installing 
Your Spa 
Wra
p Fir
eplace
www.calspas.com
7
Safe and satisfactory operation of your new fireplace spa wrap depends upon its proper installation. Installation, 
adjustments and service must be performed by L.M.S. qualified installers and service technicians to ensure 
proper operation and prevent accidents.
LP Gas Requirements
Check the rating plate to make sure the gas supply you are hooking up to is the gas type the fireplace is 
manufactured for.
IMPORTANT WARNING: All Cal Flame s and fireplaces are manufactured with the highest regard to safety. For 
this reason, Cal Flame s and fireplaces are either manufactured to operate on liquid propane (LP) or natural 
gas (NG) and cannot be converted. To verify the fireplace’s operating fuel, remove the bottom drip pan and 
check serial number label on the left. Either LP or NG will be marked on the operating tab, indicating the proper 
operating fuel. Attempting to convert a Cal Flame fireplace from one fuel to another may result in serious injury 
and void the warranty coverage.
If you do not have an updated filler valve on your existing propane tank, you will need to purchase one at your 
local hardware store, as you will not be allowed to refill the tank at any filling station.
LP Gas Hook Up: An enclosure for an LP gas cylinder shall be vented by openings at the level of the cylinder 
valve and at floor level. The effectiveness of the opening(s) for purposes of ventilation shall be determined with 
the LP-gas supply cylinder in place. This shall be accomplished in one of the following manners:
One side of the enclosure shall be completely open.
• 
Enclosures that have four sides, complete with a top and bottom:
• 
At least two ventilation openings at cylinder valve level shall be provided in the sidewall, equally sized, 
• 
spaced at 180˚ (3.14 rad), and unobstructed. Each opening shall have a total free area of not less than 
fi” square inch per pound (7.1 cm≈/kg) of stored fuel capacity, and not less than a total free area of 10 
square inches (64.5 cm≈).
Ventilation opening(s) shall be provided at floor level and shall have a total free area of not less than 
• 
fi square inch per pound (7.1 cm≈/kg) of stored fuel capacity and not less than a total free area of 10 
square inches (64.5cm≈). If ventilation openings at floor level are in a sidewall, there shall be at least 
two openings. The bottom of the openings shall be at floor level and the upper edge no more than 5 
inches (127 mm) above the floor. The openings shall be equally sized, spaced at 180˚ (3.14 rad) and 
unobstructed.
Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 inch (3.2 mm) 
• 
diameter rod.
For plumbed-in LP installation, use a convertible regulator and set it for LP gas.
LP Gas Supply Pressure: 
Maximum line pressure for plumbed-in propane is 14” W.C (3.5 kPa). Minimum 
line pressure for propane is 11” W.C.
LP Gas Pressure Regulator: The unit must be used with the gas pressure regulator. The regulator will control 
and maintain a uniform gas pressure in the manifold. The burner orifices have been sized for the gas pressure 
delivered by the regulator.
LPG Cylinder Specification: Any LP gas supply cylinder used with this fireplace must be approximately 12 
inches in diameter and 18 inches high. The maximum fuel capacity is 20 lbs. of propane, or 5 gallons. Full 
cylinder weight should be approximately 38 lbs. (43.7 lbs. nominal water capacity.) Always use the cylinder dust 
cap on the cylinder valve outlet during transport and when the cylinder is not connected to the fireplace.
Transporting the LP Gas Supply Cylinder: Only one cylinder should be transported at a time. Transport 
cylinder in an upright and secure manner with control valve turned off and the dust cap in place.
Installing Your Spa Wrap Fireplace