SPX Cooling Technologies 05-116E User Manual

Page of 36
11
Mechanical Equipment:
The fluid cooler is designed to operate at full speed and half speed. 
Warranty  is  void  if  the  tower  is  operated  at  speeds  which  cause 
damaging vibrations to the tower and associated equipment. When
utilizing a variable frequency drive, the tower must be tested across
the full range of speeds and checked against CTI guidelines for ex-
cessive vibration. Speed ranges not meeting these guidelines must 
be locked out in the VFD.
Always  shut  off  electrical  power  to  the  tower  fan  motor  prior  to 
performing any maintenance on the tower. Any electrical switches 
should be locked out and tagged out to prevent others from turning
the power back on.
1.   If equipped, check oil level in accordance with the Geareducer User 
Manual  for the Geareducer. (Although the Geareducer was filled to the 
proper level at the factory, tipping during shipment and hoisting may 
have caused some loss of oil.) If oil is required, fill Geareducer to the 
proper level with approved lubricant. (See Geareducer User Manual 
Check oil level at the Geareducer or dipstick (standpipe located on fan 
deck, if so equipped) to confirm that the proper level is indicated.
2.   On double-flow models—MHF706 and MHF707—install fan cylinder 
and two-piece fan guard according to the installation drawing shipped 
with the fluid cooler. 
Improper installation of the fan cylinder and fan guard will destroy the 
structural integrity of the fan guard. Failure of the fan guard could allow 
operating or maintenance personnel to fall into the rotating fan.
3.   Spin  the  fan(s)  manually  to  assure  that  all  fan  blades  properly 
clear  the  inside  of  the  fan  cylinder.  If  equipped,  observe  the  ac-
tion  of  the  coupling  (or  drive  shaft  couplings)  to  be  sure  that  the 
motor  and  Geareducer  are  properly  aligned.  If  necessary,  cor-
rect  the  alignment  in  accordance  with  the  included  manual. 
For belt drive equipped models observe the action of the sheaves and 
belts to be sure that the motor is properly aligned with the fan sheave. 
See Belt Tensioning and Sheave Alignment on pages 22 thru 24.
 Warning
Installation
 Warning
 Warning