SPX Cooling Technologies 05-116E User Manual

Page of 36
9
•  Do not start the motor more than 
six times per hour. Short cycling 
the tower will cause fuses, breakers or O.L.s to operate and will 
decrease motor life.
When using a two-speed starter: 
•  Motor rotation must be the same at slow speed and high speed.
•  Single winding motor requires a starter with a shorting contactor.
•  Two-winding  motor  requires  a  starter  with  out  a  shorting 
contactor.
•  All  two-speed  starters  must  have  a  20  second  time  delay  relay 
when switching from high speed to low speed.
•  Do  not  start  the  motor  more  than 
six  times  per  hour  (each  low 
speed start and each high speed start count as one start).
When using a VFD:
Before beginning, ensure that the motor is rated for “Inverter Duty” 
per NEMA MG-1, part 31.
•  Set  the  VFD  solid  state  overload  protection  to  119%  of  motor 
nameplate  amps  and  set  “maximum  current  parameter”  in  the 
VFD to motor nameplate amps. “Maximum current parameter” will 
reduce fan speed and limit amp draw to nameplate amps during 
cold weather operation. If furnished with a mechanical O.L. set this 
at 110% over motor nameplate amps.
•  Motor rotation must be the same in both VFD mode and By-pass 
mode.
•  If cable distance between the VFD and motor is greater than 100 
feet a DV/DT output filter is recommended to avoid damage to the 
motor. 100 feet distance is based on our field experience, the VFD 
manufacture may state different distances and distance does vary 
depending on the VFD manufacture.
•  Program the VFD for variable torque output. Flux vector and con-
stant torque modes may damage the gearbox.
•  Do not start and stop the motor using the safety switch at the motor. 
If the drive is being commanded to run and the load side is cycled 
ON and OFF with the safety switch this may damage the VFD.
Using a VFD in cooling applications has advantages over traditional single 
or two speed motor control. A VFD can reduce the cost of electrical en-
ergy being used and provide better temperature control. In addition, it 
reduces the mechanical and electrical stress on the motor and mechanical 
Installation
Note