Chapter 5 Troubleshooting
 
IM-83/84/86-H 
5-3
 
Flow Controllers with Motor-operated Rotary Valves 
 
 
Problem 
Possible Cause 
Solution 
 
 
 
Valve “hunts” back and forth 
continuously 
Pressure differential too great 
 
Motor coupling set screws loose 
 
Valve motor failure 
Reduce pressure 
 
Tighten set screws 
 
Replace motor 
 
 
 
Valve rotates continuously 
Limit switch out of adjustment or bro-
ken 
 
Microprocessor failed 
Adjust or replace switch 
 
 
Replace microprocessor 
 
 
 
Valve does not rotate 
Contaminant blocking valve 
 
Motor fuse blown 
Remove blockage 
 
Replace 1 amp fast blow fuse on 
motor valve board 
 
 
 
Flow reading is erratic 
Inlet filter screen clogged 
Clean or replace screen 
 
 
 
Reads full scale with no flow or 
with valve shut 
Defective sensor 
 
Q1 shorted 
 
U10 failed 
Return to factory for replacement 
 
Replace with same type part 
 
Replace with same type part 
 
 
 
Flow does not match set point 
within specifications 
Insufficient pressure differential 
Increase pressure or reduce set 
point