Selection and protection of a motor
(2) Use two types motors (Pr. 450) 
⋅ Set Pr. 450 Second applied motor to use two types motors with one inverter.
⋅ When "9999" (initial value) is set, no function is selected.
⋅ When Pr. 450 
≠ 9999, turning the RT signal ON makes the following parameter valid.
REMARKS
⋅ When performing offline auto tuning, set "3, 7, 8, 13, 17, 18, 23, 33, 43, 53" in Pr. 71.
(Refer to page 189 for offline auto tuning)
⋅ For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically changed
according to the Pr. 71 setting as follows.
REMARKS
⋅ The RT signal acts as the second function selection signal and makes the other second functions valid. 
(Refer to page 235)
⋅ The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), you can assign the RT signal to the other terminal.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
 CAUTION
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
♦ Parameters referred to 
Pr. 0 Torque boost  
 Refer to page 146
Pr. 12 DC injection brake operation voltage  
 Refer to page 203
Pr. 80 Motor capacity, Pr. 81 Number of motor poles, Pr. 453 Second motor capacity, Pr. 454 Number of second motor poles  
 Refer to page 148
Pr. 82 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 455 to Pr. 463, Pr. 859, Pr. 860 (Motor constant)  
 Refer to page 189
Pr. 95 Online auto tuning selection, Pr. 574 Second motor online auto tuning  
 Refer to page 199
Pr. 451 Second motor control method selection, Pr. 800 Control method selection  
 Refer to page 92
Pr. 100 to Pr. 109 (Adjustable 5 points V/F)  
 Refer to page 164
Pr. 71
Standard Motor Setting
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44
Constant Torque Motor Setting
1, 13 to 18, 50, 53, 54
Pr. 0
3%
2%
Pr. 12
4%
2%
Function
RT signal ON 
(second 
motor)
RT signal 
OFF (first 
motor)
Applied motor
Pr. 450
Pr. 71
Control method selection
Pr. 451
Pr. 800
Motor capacity
Pr. 453
Pr. 80
Number of motor poles
Pr. 454
Pr. 81
Motor excitation current
Pr. 455
Pr. 82
Rated motor voltage
Pr. 456
Pr. 83
Rated motor frequency
Pr. 457
Pr. 84
Motor constant (R1)
Pr. 458
Pr. 90
Motor constant (R2)
Pr. 459
Pr. 91
Motor constant (L1)
Pr. 460
Pr. 92
Motor constant (L2)
Pr. 461
Pr. 93
Motor constant (X)
Pr. 462
Pr. 94
Auto tuning setting/status
Pr. 463
Pr. 96
Online auto tuning selection
Pr. 574
Pr. 95
Torque current
Pr. 860
Pr. 859
Function
RT signal ON 
(second 
motor)
RT signal 
OFF (first 
motor)