Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)
4.7.3
Handling of high-speed counters
High-speed counters in FX
3G
/FX
3GC
 PLCs operate in the same way as high-speed counters in FX
3U
/FX
3UC
 PLCs.
For details, refer to Subsection 4.8.3.
4.7.4
Current value update timing and comparison of current value
1. Current value update timing
When pulses are input to an input terminal for a high-speed counter, the high-speed counter executes up-counting or
down-counting. The current values of devices are updated when counting is input.
2. Comparison of the Current value
The following two methods are available to compare and output the current value of a high-speed counter.
1) Using the comparison instruction (CMP), zone comparison instruction (ZCP) or comparison contact instruction
Use the comparison instruction (CMP), band comparison instruction (ZCP) or contact comparison instruction if the
comparison result is necessary at counting. Use these instructions only when high-speed processing is not
required because these instructions are processed in the operation cycle of the PLC, and operation delay is
generated before the comparison output result is obtained.
If it is necessary to execute comparison to update an output contact with the high-speed counter's changing value,
use comparison instructions for high-speed counters HSCS, HSCR and HSZ.
2) Using comparison instructions for high-speed counters (HSCS, HSCR or HSZ)
The comparison instructions for high-speed counters (HSCS, HSCR and HSZ) execute a comparison and output
the comparison result during high-speed counting. These instructions have limitations on the number of
simultaneously driven instructions as shown in the following table.
When an output relay is specified for the comparison result, the comparison result is directly updated at the ON/
OFF status of the output regardless of the output refresh by END instruction.
Mechanical operation delay (about 10 ms) cannot be avoided in a relay output type PLC. Use a transistor output
type PLC.
4.7.5
Related devices
1. Devices used to switch the counting direction of 1-phase 1-count input counters
Instruction
Limitation in number of instructions driven at same time
HSCS
6 instructions
HSCR
HSZ
Type
Counter No.
Specifying device
Up-counting
Down-counting
1-phase 
1-counting input
C235
M8235
OFF
ON
C236
M8236
C237
M8237
C238
M8238
C239
M8239
C240
M8240
C241
M8241
C242
M8242
C243
M8243
C244
M8244
C245
M8245