Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)
4.7.7
Response frequency of high-speed counters
1. Response frequency and overall frequency
When any of the following functions/instructions is used, the overall frequency is restricted regardless of the operand
of the instruction.
Consider this restriction when examining the system or creating programs, and observe the specified overall
frequency range.
• When two or more high-speed counters are used
• When the HSCS, HSCR, HSZ, PLSY, PLSR, DSZR, TBL
*1
, ZRN, PLSV, DRVI or DRVA instruction is used
• When the pulse width/pulse period measurement function is used.
*1
*1.
This function is supported only in FX
3G
/FX
3GC
 PLCs.
In FX
3S
 PLC
*2.
Number of axes used in the following positioning instructions:
PLSY (FNC 57), PLSR (FNC 59), DSZR (FNC150), ZRN (FNC156), PLSV (FNC157), DRVI (FNC158), DRVA
(FNC159)
In FX
3G
/FX
3GC
 PLCs
*3.
Number of axes used in the following positioning instructions:
PLSY (FNC 57), PLSR (FNC 59), DSZR (FNC150), TBL (FNC152), ZRN (FNC156), PLSV (FNC157), DRVI
(FNC158), DRVA (FNC159)
2. Calculation of the total frequency
Obtain the overall frequency using the following expression:
Total frequency 
 [(Sum of used frequency of 1-phase counters) + (Sum of used frequency of 2-phase counters)]
Counter type
Response 
frequency
Overall frequency determined by condition of used instruction
When HSCS, HSCR or HSZ 
instruction is not used
When HSCS, HSCR or HSZ instruction is 
used
1-phase
1-counting 
input
C235, C236, C241
60kHz
200 kHz
 - Number of positioned axes
*2
x 40 kHz
60 kHz
 - Number of positioned axes
*2
 x 5 kHz
C237, C238, C239, 
C240, C242, C243, 
C244, C245
10kHz
1-phase
2-counting 
input
C246
60kHz
C247, C248, 
C248(OP), C249, 
C250
10kHz
2-phase
2-counting 
input
C251
30kHz
C252, C253, C254,
C253(OP), C255
5kHz
Counter type
Response 
frequency
Overall frequency determined by condition of used instruction
When HSCS, HSCR or HSZ 
instruction is not used
When HSCS, HSCR or HSZ instruction is 
used
1-phase
1-counting 
input
C235, C236, C238,
C239, C241
60kHz
200 kHz
 - (Number of positioned axes
*3
+ Number of pulse width/period
measurement inputs)
x 40 kHz
60 kHz
 - (Number of positioned axes
*3
 x 5 kHz)
 - (Number of pulse width/period
 measurement inputs x 20 kHz) 
C237, C240, C242,
C243, C244, C245
10kHz
1-phase
2-counting 
input
C246, C248(OP)
60kHz
C247, C248, 
C249,C250
10kHz
2-phase
2-counting 
input
C251, C253(OP)
30kHz
C252, C253, C254,
C254(OP), C255
5kHz