Mitsubishi Electronics FX3G User Manual

Page of 964
460
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
16 External FX Device – FNC 80 to FNC 89
16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion
16.3
FNC 82 – ASCI / Hexadecimal to ASCII Conversion
Outline
This instruction converts hexadecimal code into ASCII code.
On the other hand, BINDA (FNC261) instruction converts binary data into ASCII code, and ESTR (FNC116) instruction
converts binary floating point data into ASCII code.
→ For BINDA (FNC261) instruction, refer to Section 29.6.
→ For ESTR (FNC116) instruction, refer to Section 18.4.
1. Instruction format
2. Set data
3. Applicable devices
S
1: This function is supported only in FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 PLCs.
S
2: This function is supported only in FX
3U
/FX
3UC
 PLCs.
Explanation of function and operation
1. 16-bit operation (ASCI and ASCIP)
"n" hexadecimal code characters (digits) stored in 
 and later are converted into ASCII code, and then stored to
the devices 
 and later.
The 16-bit mode and 8-bit mode options are available for this instruction. For operation in each mode, refer to the
proceeding pages.
Operand type
Description
Data type
Head device number storing hexadecimal code to be converted
16-bit binary
Head device number storing converted ASCII code
Character string
(only ASCII code)
n
Number of characters (digits) of hexadecimal code to be converted [setting range: 1 to
256]
16-bit binary
Oper-
and 
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special 
Unit
Index
Con-
stant
Real 
Number
Charac-
ter String
Pointer
X Y M T C S D .b KnX KnY KnM KnS T C D
R
U \G
V Z Modify K H
E
" "
P
S1
S2
S1
S2
n
S1
P
FNC 82
ASCI

Mnemonic
Operation Condition
16-bit Instruction
7 steps ASCI
ASCIP
Mnemonic
Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
S
1
 ‚
  S
  D
S
1
 ‚
  S
S
2
 ‚
  D
   
S
   
D
FNC 82
ASCI
n
Command
input