30.7 FNC276 - MODBUS Read/Write Instruction
30.7.1 Command Code and Command Parameters
The following table shows the required command parameters for each command code.
 
1H
Read Coils
MODBUS Address:
0000H~FFFFH
Device Count:1~2000
PLC Destination Device (head address)
Applicable Devices D•R•M•Y•S
Block Length
(
+  15)
÷
16
*1
2H
Read Discrete 
Inputs
MODBUS Address:
0000H~FFFFH
Device Count:1~2000
PLC Destination Device (head address)
Applicable Devices D•R•M•Y•S
Block Length
(
+  15)
÷
16
*1
3H
Read Holding 
Register
MODBUS Address:
0000H~FFFFH
Device Count:1~125
PLC Destination Device (head address)
Applicable Devices D•R
Block Length
4H
Read Input 
Register
MODBUS Address:
0000H~FFFFH
Device Count:1~125
PLC Destination Device (head address)
Applicable Devices D•R
Block Length
5H
Write Single Coil
MODBUS Address:
0000H~FFFFH
0 (fixed)
PLC Source Device (head address)
Applicable Devices
D•R•K•H•M•X•Y•S
(D•R•M•X•Y•S can be
indexed.)
Block Length
1 Point
6H
Write Single 
Register
MODBUS Address:
0000H~FFFFH
0 (fixed)
PLC Source Device (head address)
Applicable Devices
D•R•K•H
(D•R can be indexed.)
Block Length
1 Point
7H
Read Exception 
State 
(Available only 
in FX
3U
 and 
FX
3UC
 PLCs.)
0 (fixed)
0 (fixed)
PLC Destination Device (head address)
Applicable Devices D•R
Block Length
1 Point
8H
Diagnosis 
(Available only 
in FX
3U
 and 
FX
3UC
 PLCs.)
Sub-function: 0H
Loop-back Test
Sub-function Data 
(loop-back data):0~65535
Loop-back Test Data 
(Slave response: echo of 
)
Applicable Devices D•R
Block Length
1 Point
Sub-function: 1H
Restart
Communication
Sub-function Data:
0x0000: Do Not Reset 
Event Log
0xFF00: Reset Event Log
(Slave response: echo of 
)
Applicable Devices D•R
Block Length
1 Point
Sub-function: 2H
Return
Diagnostic Register
0 (fixed)
PLC Destination Device (head address)
Applicable Devices D•R
Block Length
1 Point
Sub-function: 3H
Change ASCII Input
Delimiter
Sub-function Data (ASCII
Mode End of Message
Character): 00H~FFH
(Slave response: echo of 
)
Applicable Devices D•R
Block Length
1 Point
Sub-function: 4H
Force Listen Only
Mode
0 (fixed)
0 (fixed)
Applicable Devices D•R
Block Length
0
Sub-function: AH
Clear Counter and
Diagnostic Register
0 (fixed)
(Slave response: echo of 
)
Applicable Devices D•R
Block Length
1 Point
  
S
1
  
S
2
  
S
3
  
S
4
  D
  
S
3
  
S
3
  
S
3
  
S
3
  
S
3
  
S
3
  
S
3
  
S
3