Mitsubishi Electronics FX3G User Manual

Page of 964
88
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.1 Device Number List
High-speed counter
1-phase 1-counting input
Bi-directional (32 bits)
C235 to C245
8 points maximum can be used among C235 to C255 [latched
(battery backed) type].
The setting can be changed between the latched (battery
backed) type and the non-latch type using parameters.
−2,147,483,648 to +2,147,483,647 counts
Hardware counter
*1
1 phase: 100 kHz 
× 6 points, 10 kHz × 2 points
2 phases: 50 kHz (1 edge count), 
50 kHz (4 edge count)
Software counter
1 phase: 40 kHz
2 phases: 40 kHz (1 edge count), 
10 kHz (4 edge count)
Section 4.8
1-phase 2-counting input
Bi-directional (32 bits)
C246 to C250
2-phase 2-counting input
Bi-directional (32 bits)
C251 to C255
Data register (32 bits when used in pair form)
General type (16 bits) 
[variable]
D0 to D199
200 points
The setting can be changed between the latched
(battery backed) type and the non-latched type
using parameters.
Section 4.9
latched (battery backed) 
type (16 bits)
 [variable]
D200 to D511
312 points
latched (battery backed) 
type (16 bits)
 [fixed] <file register>
D512 to D7999
<D1000 to 
D7999>
7488 points
<7000
points>
Among the 7488 fixed latched (battery backed)
type data registers, D1000 and later can be set as
file registers in units of 500 points.
Special type (16 bits)
*2
D8000 to D8511
512 points
Chapter 37
Index type (16 bits)
V0 to V7, Z0 to Z7
16 points
Section 4.11
Extension register/Extension file register
Extension register 
(16 bits)
R0 to R32767
32768 points latched (battery backed)
Section 4.10
Extension file register 
(16 bits)
ER0 to ER32767
32768 points
Available only while a memory cassette is
mounted
Pointer
For jump and branch call
P0 to P4095
4096 points
For CJ and CALL instructions
Section 4.12
Input interrupt
Input delay interrupt
I0
 to I5
6 points
Timer interrupt
I6
 to I8
3 points
Counter interrupt
I010 to I060
6 points
For HSCS instruction
Nesting
For master control
N0 to N7
8 points
For MC instruction
Constant
Decimal (K)
16 bits
−32768 to +32767
Chapter 5
32 bits
−2,147,483,648 to +2,147,483,647
Hexadecimal (H)
16 bits
0 to FFFF
32 bits
0 to FFFFFFFF
Real number (E)
32 bits
−1.0 × 2
128
 to 
−1.0 × 2
−126
, 0, 1.0 
× 2
−126
 to 1.0 
× 2
128
Both the decimal point expression and the exponent expression
are available.
Character string (" ")
Character string
Specify characters by quotation marks.
In a constant of an instruction, up to 32 half-width characters are
available.
*1.
When the FX
3U
-4HSX-ADP is connected to an FX
3U
 PLC, the maximum input frequency is set as follows:
1 phase: 200 kHz
2 phases: 100 kHz (1 edge count). 100 kHz (4 edge count)
*2.
For supported functions, refer to Chapter 37.
For handling of the latched (battery backed) area, refer to Section 2.6.
Device name
Description
Reference