Mitsubishi Electronics FX3G User Manual

Page of 964
899
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.4 Error Code List and Action
31
FNC277
-F
NC2
79
Da
ta
 
Trans
fer 3
32
FNC28
0-F
NC
289
H
igh-Speed 
Process
ing 2
33
FNC2
90-
FNC299
Ex
tensi
on Fi
le
 
Register C
ontrol
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt 
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
Inform
ati
on
B
Ex
ecuti
on
 T
imes
Operation error [M8067(D8067)]
6762
Continues
operation
Port specified by inverter communication instruction is 
already used in another communication.
Check to make sure the port is not specified by another 
instruction.
6763
1) Input (X) specified by a DSZR, DVIT or ZRN 
instruction is already used in another instruction.
2) The interrupt signal device for a DVIT instruction is 
outside the allowable setting range.
1) Check to make sure the input (X), as specified by a 
DSZR, DVIT or ZRN instruction, is not being used for 
the following purposes:
-
Input interrupt (including the delay function)
-
High-speed counter C235 to C255
-
Pulse catch M8170 to M8177
-
SPD instruction
2) Check the contents of D8336 for the correct interrupt 
signal specification for a DVIT instruction.
6764
Pulse output number is already used in a positioning 
instruction or pulse output instruction (PLSY, PWM, 
etc.).
Check to make sure the pulse output destination is not 
being driven by another positioning instruction.
6765
Number of applied instruction exceeds limit.
Verify that the number of times that applied instructions 
are used in the program does not exceed the specified 
limit.
6770
Memory access error
When the memory cassette is used, check whether it is 
mounted correctly.
If the problem persists or if the memory cassette is not 
used, something may be malfunctioning inside the PLC. 
Consult your local Mitsubishi Electric representative.
6771
Memory cassette is not connected.
Check for the correct attachment of the memory cassette.
6772
Memory cassette is protected against writing.
The write-protect switch of the memory cassette was set 
to ON when data was transferred
to the flash memory. Set the protect switch to OFF.
6773
Access error to memory cassette during writing in RUN 
mode
While data was written in the RUN mode, data was 
transferred to (read from or written to) the memory 
cassette.
USB communication error [M8487(D8487)]
8702
Continues 
operation
Communication character error
Confirm the cable connection between the programming 
device and the PLC. This error may occur when a cable 
is disconnected and reconnected during PLC monitoring.
8703
Communication data sum check error
8704
Data format error
8705
Command error
8730
Memory access error
When the memory cassette is used, check whether it is
mounted correctly.
If the problem persists or if the memory cassette is not
used, something may be malfunctioning inside the PLC.
Consult your local Mitsubishi Electric representative.
Special block error [M8449(D8449)]
020
*1
Continues 
operation
General data sum error
Verify that extension cables are correctly connected.
021
*1
General data message error
022
*1
System access error
025
*1
Access sum error in other station via CC-Link
026
*1
Message error in other station via CC-Link
030
*1
Memory access error
When the memory cassette is used, check whether it is 
mounted correctly.
If the problem persists or if the memory cassette is not 
used, something may be malfunctioning inside the PLC. 
Consult your local Mitsubishi Electric representative.
080
*1
FROM/TO error
This error occurs in the execution of operation.
Review the program and check the contents of the 
operands used in applied instructions.
Verify that specified buffer memories exist in the 
counterpart equipment.
Verify that extension cables are correctly connected.
090
*1
Peripheral equipment access error
Check the cable connection between the 
programming panel (PP) / programming device and 
the PLC.
Verify that extension cables are correctly connected.
*1.
The unit number 0 to 7 of the special function unit/block error is put in  .
Error 
code
PLC operation at 
error occurrence
Contents of error
Action