York THGD18 THRU 60 User Manual

Page of 30
397763-YTG-B-0508
2
Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change 
without notice. Certified dimensions will be provided upon 
request.
Physical and Electrical Data
MODEL
THGD18
S41S1
THGD24
S41S1
THGD30
S41S1
THGD36
S41S1
THGD42
S41S1
THGD48
S41S1
THGD60
S41S1
Unit Supply Voltage
208-230V, 1
φ, 60Hz
Normal Voltage Range 
1
187  to 252
Minimum 
Circuit 
Ampacity
9.6  12.0 15.4 19.6 28.6 30.9 37.4 
Max. Overcurrent Device Amps 
2
15 20 25 30 50 50 60 
Min. Overcurrent Device Amps 
3
15 15 20 20 30 35 40 
Compressor 
Type 
Recip Recip Recip Recip Scroll Scroll Scroll 
Compressor Amps
Rated 
Load
7.12  8.9  11.65 14.72 21.76 23.61 28.79 
Locked 
Rotor
47.0 48.0 60.0 83.0 105.0 
150.0 150 
Crankcase 
Heater
Yes Yes Yes Yes  No  No  No 
Fan Motor Amps
Rated Load
0.70 
0.80 
0.80 
1.5 
1.5 
1.5 
1.5 
Fan 
Diameter 
Inches
24 24 24 24 24 24 24 
Fan Motor
Rated 
HP
1/10 1/8 1/8 1/4 1/4 1/4 1/4 
Nominal 
RPM
825 1075 
1075 850 850 850 850 
Nominal 
CFM
2200 2900 3100 3800 3200 3000 3000 
Coil
Face Area Sq. Ft.
15.7 
18.3 
21.0 
23.58 
23.58 
23.58 
23.58 
Rows 
Deep
1 1 1 1 1 2 2 
Fin 
Inches
22 22 22 22 22 18 18 
Liquid 
Line 
Set 
OD 
(Field 
Installed)
3/8 3/8 3/8 3/8 3/8 3/8 3/8 
Vapor 
Line 
Set 
OD 
(Field 
Installed)
3/4 3/4 3/4 3/4 7/8 7/8 7/8 
Unit Charge (Lbs. - Oz.) 
4
6 - 5 
8 - 7 
9 - 12 
9 - 15 
9 - 12 
13 - 9 
13 - 6 
Charge 
Per 
Foot, 
Oz.
.62 .62 .62 .62 .67 .67 .67 
Operating 
Weight 
Lbs.
172 184 196 208 208 275 280 
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, 
add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B
C
Liquid
Vapor
18
28
34
34
3/8”
3/4”
24
32
34
34
30
36
34
34
36
40
34
34
42
40
34
34
7/8”
48
40
34
34
60
40
34
34