Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
9
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
NEW 2 way gas driven VRF with electrical 
power generator
SANYO’s  ECO  G  Power  is  a  revolution  in  air 
conditioning  design.  Fitted  with  a  permanent 
magnet,  non-bearing  type  generator,  it  is  the  first 
VRF  system  that  can  supply  heating,  cooling,  hot 
water and now also a supply of electrical power.
Each  ECO  G  Power  unit  has  a  4.0kW  generator,  which 
provides  enough  electricity  to  power    8  computers  or 
other applications. 
•  Innovative  technology  that  reduces  CO
2
  emissions  by  up    to 
30%
•  Heat  pump  air  conditioning  system  providing  cooling  
or heating
•  Can  provide  both  electricity  and  hot  water  in  heating  and 
cooling mode
• Up to 4kW electricity generated
• Very efficient generator
•  Hot  water  provided  when  cooling  or  heating  when  outside 
ambient air temperature is above 7°C
• 22kW hot water generation capacity
• 20HP model provides 56kW cooling or 63kW heating
• Can connect to up to 36  indoor units 
• 200m maximum allowable piping length (L1) (equivalent - refer 
to technical manual)
• IU/OU capacity ratio 50 - 130%
ECO G Power - GHP with electricity generation 
& hot water supply
0
10
20
30
40
50
60
70
80
90
100
Air conditioning load (%)
4.5
4
3.5
3
2.5
2
1.5
1
0.5
0
Pr
oduc
tion of elec
tr
icit
y (kW
)
Production of electricity
Generates  from  2kW  to  4kW  depending  on  air  conditioning 
load
Dimensions ECO G Power
High power 
engine
Line linkage 
inverter
Power generator
•  permanent 
magnet type
•     non-bearing
Double clutch 
compressor
NEW
HP
20
33
36
40
45
Model
SGP-EGW190M2G2W
SGP-EW120M2G2W
SGP-EW150M2G2W
SGP-EGW190M2G2W
SGP-EGW190M2G2W
SGP-EGW190M2G2W
SGP-EGW190M2G2W
SGP-EGW190M2G2W
SGP-EW240M2G2W
Capacity
Cooling
kW
56.0
91.50
101.00
112.00
127.00
Heating 
STD
kW
63.0
103.0
113.00
126.00
143.00
Heating  Low temp*1
67.0
109.50
120.00
134.00
142.00
Hot water
22.0
34.0
38.0
44.0
47 .00
Power generater capacity at 
rating
kW
DC 2.5 (Max 4.3)
Electricity
Cooling
kW
1.35
2.20
2.70
Heating
kW
1.01
2.02
2.55
Gas consumption
Cooling
kW
44.0 (38.3)*
68.50
75.60
88.00
104.90
Heating STD
kW
48.7 (43.0)*
76.80
84.80
97.40
101.00
Heating 
LOW
62.1 (56.4)*
98.90
109.40
124.20
121.30
COP Air conditioning only
Cooling
1.33 (1.41)*
1.29
1.23
1.18
Heating
1.34 (1.43)*
1.31
1.30
1.27
1.38
AVE
1.34 (1.42)*
1.30
1.25
1.28
Max COP (Inc generater, hot water) 
Cooling
1.78
1.81
1.80
1.78
1.69
Height
Height
mm
2,248
Width
1,800
1,800 + 100 (Min distance) + 1,800
Depth
1,000 (+60)
Weight
kg
875
1,660
1,685
1,740
1,720
Starter amperes
A
30
Pipe
Gas
Inches (mm)
1 1/8 (28.58)
1 3/8 (34.92)
1 5/8 (41.27)
Liquid
5/8 (15.88)
3/4 (19.05)
Balance
3/8 (9.52)
Pipe fuel gas 
R3/4 (bolt, thread)
Pipe exhaust drain port
mm
ø25 rubber hose
Operation sound
dB(A)
58
61
63
Indoor/outdoor capacity ratio
50-130%
Number of indoor connections*
32
48
Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details. 
Please refer to tube sizing charts for pipe selections and pipe length parameters. 
Capacity Hot Water is available when outside ambient air temperature is above 7˚C.
Service Clearances for installation
Top View
Rear View
Front View
Left Side View
at least 2000
(Units: mm)
Rear
(refrigerant tubing)
Rear
(refrigerant tubing)
at
 le
as
60
0
at
 le
as
60
0
at
 le
as
10
00
at
 le
as
10
00
22
50
271
54
147
207
242
275
312
461
27
83
99
13
8
16
3
17
8
19
3
55
5
at least 
100
at least 
100
1000 (external)
1800 (external)
1040 (suspension holes)
1100 (frame width)
ø736
at least 
100
at least 
350
400
(1
69
)
22
48
    
 5 
10
14
(a
nc
ho
r p
itc
h)
1000
(anchor pitch)
at least 
350
Front View
Front View
(Single-unit installation)
(Multi-unit series installation)
Gas refrigerant pipe (Gas tube)
ø28.58
Size (mm)
ø15.88
ø9.52
ø28
ø28
ø20
ø28
ø40
G: R3/4
Rp3/4
Rp3/4
OD:
Length:
1
Liquid refrigerant pipe (Liquid tube)
2
Refrigerant balance pipe (Balance tube)
3
Exhaust gas drain hose
4
Electrical power supply port
5
Inter-unit cable port
6
Inverter cable port
7
Inverter cable port
8
Fuel gas port
9
Condensation drain opening
10
Rain and condensation outlet
11
Engine exhaust outlet
12
Suspension holes 4 - ø20
13
Anchor holes 4 - ø24
14
Segment display
15
Coolant intake (top)
16
Vent
17
Hot water intake
18
Hot water outlet
19
12
14
16
9
11
17
13
15
8
3
4
2
10
1
19
18
7
5
6
Generate  electricity  during  heating  or  cooling 
operation
Generate  electricity  and  air  conditioning  (heating  or  cooling) 
at  the  same  time  by  using  remaining  engine  power.  ECO  G 
Power can generate from 2.3 to 4.0kW electricity at a generation 
efficiency of more than 40%.