Mitsubishi P240 User Manual

Page of 334
VII  Control ]
- 118 -
HWE09120
GB
(2) Heating operation
1)   When outdoor unit starts defrosting, it transmits defrost operations command to indoor unit, and the indoor unit start defrosting 
operations. Similarly when defrosting operation stops, indoor unit returns to heating operation after receiving defrost end com-
mand of outdoor unit.
2)   Defrost end condition: 12 or more minutes must pass after defrost operation or outdoor unit piping temperature. 
Refer to "-7- Defrost operation control" of [2] Controlling the Outdoor Unit for the temperature.
Heating operation 
Test run mode  
ON 
Thermostat ON 
Defrost  
operation 
3-minute restart  
prevention 
*Note 1,2 
*Note 1,2 
YES 
YES 
YES 
YES 
YES 
NO 
NO 
NO 
NO 
NO 
1. Indoor/outdoor unit fan control
2. Inverter frequency control
3. Indoor unit LEV, LEV1,LEV2 control
4. Solenoid valve control
5. 72C control
Normal operation 
Defrost operation 
4-way valve ON 
During test run mode 
1. Indoor unit fan operation at 
     Very Low speed
2. Inverter output  0Hz
3. Indoor unit LEV, LEV1 Fully closed
     LEV2 rated opening
4. All solenoid valves OFF
5. Outdoor unit fan stop
6. 72C OFF
4-way valve OFF 
Stopping the  
defrost operation 
Stopping the defrost  
operation 
Return to heating  
operation 
1. Indoor unit fan stops
2. Inverter defrost frequency control
3. Indoor unit LEV fully closed.
4. Solenoid valve control
5. Outdoor unit fan stop
6. LEV1 control
7. LEV2 fully opened.
8. 72C control
Unit in the stopped state