(3) Dry operation
Dry operation 
*Note 1 
*Note 2 
YES 
YES 
NO 
NO 
4-way valve OFF 
1. Outdoor unit (compressor)  
    intermittent operation 
2. Indoor unit fan intermittent operations  
    (Synchronized with the compressor:  
      low speed, OFF operations) 
Normal operation 
Thermostat ON 
Thermostat ON 
1. Indoor unit fan stop
2. Inverter output  0Hz
3. Indoor unit LEV, LEV1 fully closed.
    LEV2 rated opening.
4. Solenoid valve OFF
5. Outdoor unit fan stop
6. 72C OFF
 1  or  2 
*Note 1.When the indoor unit inlet temperature exceeds 18°C [64°F], the outdoor unit (compressor) and the 
             indoor unit fan start the intermittent operation simultaneously. When the indoor unit inlet temperature 
             becomes 18°C [64°F],or less, the fan always runs (at low speed). The outdoor unit, the indoor unit, 
             and the solenoid valve operate in the same way as they do in the cooling operation when the compressor 
             is turned on.
*Note 2.Thermostat is always kept on during test run mode, and indoor and outdoor unit intermittent operation 
            (ON) time is a little longer than that of normal operation.
Test run mode  
ON 
Suction temperature
    18°C[64°F]
Unit in the stopped state