Mitsubishi P240 User Manual

Page of 334
II  Restrictions ] 
- 17 -
HWE09120
GB
II Restrictions
[1] System configuration
1. Table 
of 
compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units. 
1)   "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2)   If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the 
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of 
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor  
units
Composing units
Maximum total capacity 
of connectable indoor 
units
Maximum number 
of connectable in-
door units
Types of connectable in-
door units
72
 - 
 - 
 - 
36 - 93
15
P06 - P96models
R410A series indoor units
96
 - 
 - 
 - 
48 - 124
20
120
 - 
 - 
 - 
60 - 156
26
144
 - 
 - 
 - 
72 - 187
31
168
96
72
 - 
84 - 218
36
192
120
72
 - 
96 - 249
41
216
120
96
 - 
108 - 280
46
240
120
120
 - 
120 - 312
50
264
144
120
 - 
132 - 343
288
144
144
 - 
144 - 374
312
120
120
72
156 - 405
336
120
120
96
168 - 436
360
144
120
96
180 - 468