Mitsubishi P240 User Manual

Page of 334
II  Restrictions ] 
- 19 -
HWE09120
GB
2)   Remote controller wiring
*1  MA remote controller refers to MA remote controller (PAR-20MAU, PAR-21MAA), MA simple remote controller, and 
wireless remote controller.
*2  The use of cables that are smaller than 0.75mm
2
 (AWG18) is recommended for easy handling.
*3  When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
[3] Switch Settings and Address Settings
1. Switch 
setting
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected  - [7] An Example of a System 
to which both MA Remote Controller and ME Remote Controller are connected" before performing wiring work.
Set the switches while the power is turned off.
If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not 
function properly.
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line.
*2. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of 
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
*3. Turn off the power to all the outdoor units in the same refrigerant circuit.
MA remote controller
*1
ME remote controller
Cable type
Type
CVV
CVV
Number of 
cores
2-core cable
2-core cable
Cable size
0.3 to 1.25mm
2  *2
[AWG22 to 16]  
(0.75 to 1.25mm
)
   *3 
 
[AWG18 to 16] 
0.3 to 1.25mm
2  *2
 
[AWG22 to 16]  
(0.75 to 1.25mm
)
   *3 
 
[AWG18 to 16]
Maximum overall line 
length
200 m [656ft] max.
The section of the cable that exceeds 10m 
[32ft] must be included in the maximum in-
door-outdoor transmission line distance. 
Units on which to set the switches
Symbol
Units to which the power must be shut off
CITY MULTI indoor unit
Main/sub unit
IC
Outdoor units 
*3 
and Indoor units
LOSSNAY, OA processing unit 
*1
LC
Outdoor units 
*3 
and LOSSNAY
Air handling kit
IC
Outdoor units 
*3 
or field supplied air handling 
unit
ME remote controller
Main/sub remote 
controller
RC
Outdoor units 
*3  
MA remote controller
Main/sub remote 
controller
MA
Indoor units
CITY MULTI outdoor unit
*2 
OC,OS1,OS2
Outdoor units 
*3