Monessen Hearth CDVR33N/PV7 User Manual

Page of 68
CDVSC7 & CDV7 Series Gas Fireplace
0
69D3011
VenTInG InSTallaTIon     
FP2294
Side View Vent Termination
1/25/00   djt
Finish Wall
Vent 
Termination
FP94
Figure 17 - 
Side View of Final Unit Location
ReaR wall VenT InSTallaTIonS - 
Flex VenT pIpe
Follow Steps 1 and  on Page 19.
Step 3
Install the 4” (10 mm) flex vent pipe to the appliance col-
lars  described  in  “General  Information Assembling  Vent 
Pipes”, Page 1.  If the installation requires a 45° angle, 
grasp the vent pipe close to the appliance collar and bend 
to 45°. DO NOT exceed 45°. Figure 18
Install the 7” vent pipe in the same manner as Step .
noTe: There must be a 1/” (13 mm) rise in a 1”      (305 
mm) length of flex vent. 
Step 4
Assemble the flex vent to the collars on the termination as 
you did on the appliance.
FP1473
corner flex install
4/04  djt
Termination
Flex Section
Appliance Collars
FP1473
Figure 18 - 
Grasp the vent pipe close to the collar and 
bend to 45° angle. do not exceed 45°.
FP1472
rise in length
4/04  djt
Rise
FP147
Figure 19 - 
There must be a 1/2" rise per foot length
Top VenT SIDewall applICaTIon
noTe:  For  all  top  vent  installations  where  a  90°  elbow 
is the first pipe piece towards a sidewall termination (up 
and  out),  an  open-center  ringed  flue  restrictor  must  be 
installed onto the top edge of the firebox flue adapter. To 
create  this  open-center  re-
strictor,  twist  and  break  off 
the center rib of the supplied 
flue  restrictor. The  installed 
part  should  appear  similar 
to that show n in Figure 20. 
Since  it  is  very  im-
portant  that  the 
venting 
system 
maintain its balance 
between  the  com-
bustion  air  intake  and  the  flue  gas  exhaust,  certain 
limitations as to vent configurations apply and must 
be strictly adhered to.
The Vent Graph, showing the relationship between verti-
cal and horizontal side wall venting, will help to determine 
the various dimensions allowable.
Minimum clearance between vent pipes and combus-
tible materials is 3" (76 mm) on top, and 1" (25 mm) on 
the bottom and sides unless otherwise noted.
When  vent  termination  exits  through  foundations  less 
than  0”  (508  mm)  below  siding  outcrop,  the  vent  pipe 
must flush up with the siding.
It is best to locate the fireplace in such a way that mini-
mizes the number of offsets and horizontal vent length. 
The horizontal vent run refers to the total length of vent 
pipe from the flue collar of the fireplace (or the top of the 
Transition Elbow) to the face of the outer wall.
Horizontal plane means no vertical rise exists on this por-
tion of the vent assembly.
when installing the appliance as a rear vent unit, the 
90°  or  45°  Transition  elbow  attached  directly  to  the 
rear of the unit is noT InCluDeD in the following cri-
teria  and  calculations,  and  unless  specifically  men-
tioned  should  be  ignored  when  calculating  venting 
layouts.
FP2303
CDV7 rear restrictor
3/09
Figure 20 - 
Top Vent Vertical Sidewall 
Restrictor
FP303