CDVSC7 & CDV7 Series Gas Fireplace
18
69D3011
3"
1"
1"
1"
FP2288
TV rear vent
VenTInG InSTallaTIon 
Figure 14 - 
Combustible Clearances for Vent Pipe
A Minimum of 3" Clearance 
to  the  Top  Is  Required 
Along  Horizontal  Length 
until Flue Pipe Penetrates 
Outside Wall. 
A  Minimum  1" 
C l e a r a n c e   t o 
Combustibles 
P e r m i t t e d   A l l 
Around  Flue  at 
Outside Wall
VenT pIpe CleaRanCeS
Rear Vent: horizontal sections of this vent 
system require a minimum of 3" clearances 
to combustibles at the top of the flue and 
1" clearance at the sides and bottom until 
the  flue  penetrates  the  outside  wall.  

minimum 1" clearance all around the flue 
is acceptable at this point of penetration.
Vertical sections of this vent system require 
a minimum of 1" clearance to combustibles 
on all sides of the pipe.
w
a
R
n
In
G
Top Vent: horizontal sections of this vent 
system require a minimum of 3" clearances 
to combustibles at the top of the flue and 
1" clearance at the sides and bottom until 
the  flue  penetrates  the  outside  wall.  

minimum 1" clearance all around the flue 
is acceptable at this point of penetration. If 
vertical rise is 7
1
/
2
 feet or higher when top 
venting, the clearance to combustibles is 
1" on all sides of the horizontal run.
Vertical sections of this vent system require 
a minimum of 1" clearance to combustibles 
on all sides of the pipe.
w
a
R
n
In
G
1"
3"
1"1"
FP2289
RV rear vent
A  Minimum  of  3"  Clearance 
to  the Top  Is  Required Along 
Horizontal  Length  until  Flue 
Pipe  Penetrates  Outside 
Wall. 
A  Minimum  1"  Clearance 
to  Combustibles  Permitted 
All Around Flue at Outside 
Wall
FP88
FP89
CDVR Series
CDVT Series