Soleus kfihp-09 User Manual

Page of 26
 
- 15 -
 
 
 
               
Install the Outdoor Unit 
 
 
•  Install the connection pipe 
1.  Align the center of the piping flare with the valve. 
2.  Screw in the flare nut by hand and then tighten 
the nut with spanner and torque wrench refer to 
right figure. 
 
Tightening Torque Table 
 
Hex Nut Diameter 
(mm) 
Tightening Torque 
N.m) 
Φ6 15~20 
φ12 50~55 
 
 
 
 
 
 
 
 
 
 
•  Electric wiring connection 
1.  Disassemble the big handle. 
2.  Remove the wire clamp and connect the end of 
the power connection cord with screws to the  
wiring terminal board.  Be sure that the wiring  
connection is in accordance with the indoor unit’s. 
3.  Fix the wiring with wire clamp.  For the heat 
pump join the two control cords. 
4.  Make sure that the wiring has been connected securely. 
5.  Reassemble the big handle. 
 
 
 
 
 
 
 
 
NOTE: 
1.    Incorrect wiring connections will cause electrical malfunction. 
2.  Do not pull the wire when assembling it with wire clamp. 
 
 
 
 
 
 
 
 
 
Note: Exceeding tightening torque will 
          damage the flare nut.