APC Smart-UPS 8000VA Online 230V Ext Batt SUDP8000IX194 User Manual

Product codes
SUDP8000IX194
Page of 24
990-1007A, Revision 2  9/99
12
Standard System With Isolating Transformer (400 V) And SBP
System
Mains Fuse*
(Fm)
Input Cable
Transformer
Input Cable UPS
Output Cable
UPS
4kV
16A
3x2.5mm²
3x6mm²
3x6 mm²
6kV
25A
3x6 mm²
3x16 mm²
3x10 mm²
8kV
32A
3x10 mm²
3x16 mm²
3x10 mm²
10kV
40A
3x10 mm²
3x16 mm²
3x16 mm²
*Din gl Types
System
Output Cable UPS
Output Fuse SBP (Fo)
Output Cable SBP
4kV
3x4 mm²
20A
3x4 mm²
6kV
3x10 mm²
32A
3x10 mm²
8kV
3x10 mm²
40A
3x10 mm²
10kV
3x16 mm²
50A
3x16 mm²
LOAD
MAINS
L1
L2
PE
Input
Cable Tr.
Iso.Tr
.
L1
L2
Tr. Sw. cable
L
N
UPS
N
L
N
L
INPUT
CABLE
SBP
L
N
OUTPUT
CABLE
SBP
SBP
L
N
L
N
Input
cable
UPS
Output
cable
UPS
Fm
Fo
Fm
1  2  3  4
MBS CONTROL
SBP
CABLE
X010
1  2  3  4
External Run Battery Cabinet
Note:
You must attach a ferrite bead to the signal cable of the extended run battery cabinet to ensure regulatory compliance.  A ferrite
bead and its installation instructions are included in the literature kit.
For longer uninterrupted power during UPS on-battery operation, connect an extended run battery cabinet to the
Smart-UPS DP.  All connection diagrams show the UPS with an extended run battery cabinet already connected.
Detail of Smart-UPS DP with an Extended Run Battery Cabinet