Samsung Q9000 ميموري User Manual

Page of 54
50
Vacuum pump
Vacuuming pipe
1.  Completely connect the indoor/outdoor unit pipes.
2.  Connect the manifold gauge to the service valve port of the low pressure side on the outdoor unit.
3.  Execute vacuum pump for over 30 minutes.
 - If the pipe extension is larger, time of the vacuum  pump should also get longer.
4.  After degree of vacuum has been established, open the service valve ➀~➁ as shown in the illustration. 
 - Use soapsuds to check for refrigerant leakage on the  connection part of the pipes
2
1
Outdoor unit Condenser 
(PFC)
Air flow
Sensor
EEV
Compressor
Indoor unit Evaporator 
(PFE)
Service Valve
Service Valve
f
f Vacuuming air conditioner 
 - Execute vacuum pump on the manifold gauge connected to low pressure side ➁, to purge the air from the pipes and indoor unit.