Performing leak test
f
f Use leak tester or soapsuds on the pipe connection part after performing vacuum pump.
Check for 
leakage
Check for 
leakage
Test part for indoor unit
Test part for outdoor unit
f
f Before inspecting the leakage, use a torque wrench to close the cap for the service valve.(Comply with a tightening 
torque for each size of the diameter, and tighten the cap firmly to prevent any leakage.)
f
f To check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the 
connection part of the indoor/outdoor units with soap lather or liquid for leakage test.
Tightening torque for charging port cap 
(Refer to the table)
Tightening torque for body cap 
(Refer to the table)
R-22: Diameter of the screw - 7/16-20UNF
R-410A: Diameter of the screw - 1/2-20UNF
Charging 
core
Spindle
Outer 
Diameter 
(mm)
Tightening torque
Body cap 
(N•m)
Charging port 
cap (N•m)
Ø6.35
20 ~ 25
10 ~ 12
Ø9.52
20 ~ 25
Ø12.7
25 ~ 30
Ø15.88
30 ~ 35
Ø19.05
35 ~ 40
1 N•m = 10 kgf•cm