10.9 Multiple range high/low limit alarm function (option)
The procedure to use multiple range high/low limit alarm is shown below.
Range setting
・
Set the range in accordance with 8.2.9 Span (range) in the following order.
1. Set the range type to “unidirectional flow, multiple ranges selected by
external signal”.
2. Set Range 1 and Range 2 respectively.
DO setting (Note 1)
・
Set digital output 1 and 2 (DO1, DO2) function to multiple range high limit
alarm output and multiple range low limit alarm output respectively in
accordance with 8.2.18 Digital I/O.
accordance with 8.2.18 Digital I/O.
Also set the alarm output state to either of normally open or normally close.
DI
setting
・
Set digital input (DI) function to RANGE SW in accordance with 8.2.19
Digital I/O.
High/Low limit
alarm value setting
・
Set high limit alarm and low limit alarm to ON and set alarm value to high
and low alarms respectively in accordancewith 8.2.23 Flow Rate High, Low,
High-High and Low-Low limit Alarm Setting.
High-High and Low-Low limit Alarm Setting.
Set the alarm not to use to OFF.
High High/Low Low limit
alarm value setting
・
Set high-high alarm and low-low alarm to ON and set alarm value to them
respectively in accordance with 8.2.23 Flow Rate High, Low, High-High
and Low-Low limit Alarm Setting.
respectively in accordance with 8.2.23 Flow Rate High, Low, High-High
and Low-Low limit Alarm Setting.
Set the alarm not to use to OFF.
(Note 1) When setting DO using HHT AF900 (Ver2.40 or older), set alarm outputs
as below:
Multiple range high limit alarm output
SPECIAL-B,
Multiple range low limit alarm output
SPECIAL-A