 126 − 
 
6 F 8 A 0 9 3 4  
10.9 Multiple range high/low limit alarm function (option) 
The procedure to use multiple range high/low limit alarm is shown below. 
 
 
Range setting 
 
                 
 
 
 
 
                 
Set the range in accordance with 8.2.9 Span (range) in the following order. 
 
1. Set the range type to “unidirectional flow, multiple ranges selected by 
external signal”. 
2. Set Range 1 and Range 2 respectively. 
 
DO setting (Note 1) 
 
                 
 
 
 
 
                 
Set digital output 1 and 2 (DO1, DO2) function to multiple range high limit 
alarm output and multiple range low limit alarm output respectively in 
accordance with 8.2.18 Digital I/O.  
 
Also set the alarm output state to either of normally open or normally close
 DI 
setting 
 
 
Set digital input (DI) function to RANGE SW in accordance with 8.2.19 
Digital I/O
 
High/Low limit   
alarm value setting 
 
                 
 
 
 
 
                 
Set high limit alarm and low limit alarm to ON and set alarm value to high 
and low alarms respectively in accordancewith 8.2.23 Flow Rate High, Low, 
High-High and Low-Low limit Alarm Setting
 
    Set the alarm not to use to OFF. 
 
High High/Low Low limit 
alarm value setting 
 
 
Set high-high alarm and low-low alarm to ON and set alarm value to them 
respectively in accordance with 8.2.23 Flow Rate High, Low, High-High 
and Low-Low limit Alarm Setting
.  
 
Set the alarm not to use to OFF. 
 
(Note 1) When setting DO using HHT AF900 (Ver2.40 or older), set alarm outputs 
as below: 
Multiple range high limit alarm output   
SPECIAL-B, 
Multiple range low limit alarm output   
SPECIAL-A