Enviro sienna indoor gas fireplace User Manual

Page of 32
14
Initial Installation
Check draft with a match
or smoke in a 1⁄4" (6 mm)
tube located here.
M
INIMUM
 F
IREPLACE
 S
IZE
:
Description of Fireplace Dimension
Direct Vent
B-Vent 
Width
At Back
23 1⁄4” (591 mm)
23 1⁄4” (591 mm)
At Front
35” (889 mm)
35” (889 mm)
Height
With Surround Only
23 3⁄4” (603 mm)
23 3⁄4” (603 mm)
With Surround with Trim
23” (584 mm)
23” (584 mm)
Depth
With Surround Only
18” (457 mm)
19” (483 mm)
With Surround with Trim
16 1⁄2” (419 mm)
17 1⁄2” (445 mm)
B-V
ENT
 M
ODEL
:
WARNING: This appliance has been designed to operate by drawing combustion air and dilution air 
from the room. It is also designed to draw room air for proper heat circulation from the sides of the 
unit. Blocking or modifying the louvers in any way can create hazardous situations, either through poor 
venting or by overheating. It is important that this unit has sufficient air circulation for proper venting 
and combustion. Provisions must be made for the supply of adequate combustion and ventilation air. 
These openings must not be blocked. The appliance must not be connected to a chimney flue servicing 
a separate solid fuel-burning appliance.
A
UTOMATIC
 F
LUE
 G
AS
 S
PILL
 S
WITCH
 - B-V
ENT
 M
ODEL
 O
NLY
:
NOTE: This heater must be properly connected to a venting system. This heater is equipped 
with a vent safety shutoff system designed to protect against improper venting of combustion 
products.  This safety switch is located on the rear of the appliance. If the switch trips more 
than  once,  the  venting  should  be  inspected  by  a  qualified  service  technician  for  possible 
blockage or severe down draft conditions.
WARNING: Operation of this heater when not connected to a properly installed and maintained 
venting system can result in carbon monoxide (CO) poisoning and possible death.
The  draft  hood  must  be  in  the  same  pressure  zone  as 
the air inlet.  Inspect for draft from the front of the unit 
at  the  1⁄4”  tube  shown  in  Figure  18.  Check  for  a  draft 
using  smoke;  a  vacuum  or  suction  into  the  tube  will 
indicate proper drafting. If air is blowing out of the tube 
the  problem  must  be  corrected  before  the  unit  can  be 
started.
This model can be vented with 4” aluminum or stainless 
steel  flex  vent  and/or  certified  Type  B  Gas  Vent.  The 
flue  collar  of  the  appliance  will  fit  inside  of  a  standard 
4” vent and may be fastened directly to the vent. Check 
periodically that the vent is unrestricted and an adequate 
draft is present when the unit is in operation. 
Figure 18: Draft check.
Table 3: Minimum dimensions of fireplace for Sienna to be installed into.