Alliance Laundry Systems 70269701R4 User Manual

Page of 66
Exhaust Requirements
70269701
36
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Manifold Venting
While it is preferable to exhaust tumblers individually 
to the outdoors, a main collector duct may be used if it 
is sized according to Figure 11. This illustration 
indicates minimum diameters, which should be 
increased if the collector length exceeds 14 feet 
(4.3 meters) and two 90° elbows. The diameter of a 
round duct must be increased by 10% for each 
additional 20 feet (6.1 meters). Cross sectional area of 
a rectangular or square duct must be increased 20% for 
each additional 20 feet (6.1 meters). Refer to Table 4 
to determine equivalent ducting sizing. The collector 
duct may be rectangular or square in cross section, as 
long as the area is not reduced. Provisions MUST be 
made for lint removal and cleaning of the collector 
duct.
The vent collector system must be designed so the 
static back pressure measured 12 inches (305 mm) 
from the exhaust outlet does not exceed the maximum 
allowable pressure specified on the installation sticker 
on the rear of tumbler. Static back pressure must be 
measured with all tumblers vented into the collector 
operating.
NOTE: Never connect a tumbler duct at a 90° 
angle to the collector duct. Refer to Figure 10

Doing so will cause excessive back pressure, 
resulting in poor performance. Never connect two 
tumbler exhaust ducts directly across from each 
other at the point of entry to the collector duct.
With the tumbler (both pockets on stacked models) in 
operation, airflow at any point in the duct should be at 
least 1200 feet per minute (366 meters per minute) to 
ensure that lint remains airborne. If 1200 feet per 
minute cannot be maintained, schedule a regular 
inspection and cleaning of the ductwork.
The collector system must be designed so the static 
back pressure measured 12 inches (305 mm) from the 
exhaust outlet does not exceed the maximum 
allowable pressure specified on the installation sticker 
on the rear of tumbler. This must be measured with all 
tumblers vented into the collector operating.
Figure 10 
T438I