System Tests
The following system tests are performed during 
normal operation. System tests are performed at a 
minimum of every 24 hours. 
Low Voltage Detection
If the voltage between terminals TH and GND on the 
control is below 18.75VAC +/- 0.75VAC for more than 
3 seconds the ignition control will turn off the gas 
valve and will not attempt to spark. The Diagnostic 
LED will display Error Code 5.  The ignition control 
will not enter Lockout Mode if a low voltage condition 
is detected, but will enter Standby Mode and wait for 
the low voltage condition to be cleared.
If the voltage between terminals TH and GND on the 
control rises above 19.75VAC +/- 0.1VAC for at least 
3 seconds, the ignition control will then enter Start Up 
Mode.
Low Voltage Detection test is disabled during Run 
Mode.
Gas Valve
The ignition control verifies that the gas valve is 
connected.  Failure of this test results in the ignition 
control entering Lockout Mode with the Diagnostic 
LED displaying Error Code 2.
Flame Probe Tests
Unexpected Presence of Flame
The Unexpected Presence of Flame test is performed 
when no flame is expected. Failure of this test results 
in the ignition control entering Lockout Mode with the 
Diagnostic LED displaying Error Code 3. 
Flame Monitoring
During the Flame Monitoring test, the flame is 
checked to ensure the gas is being burned when the gas 
valve is on. Failure of this test will result in the 
ignition control entering Lockout Mode with the 
Diagnostic LED displaying Error Code 3. 
Diagnostic LED (DGN LED)
 
/ Error Codes
The Diagnostic LED or DGN LED is located by the 
power connector on the ignition control.  Refer to 
Figure 5
. The Diagnostic LED will indicate the status 
of the ignition control. Refer to Table 1.
The Diagnostic LED will flash error codes one half 
second on and one half second off. Error codes are 
separated by a one second pause before the code is 
repeated.
LED Color
Description
Orange-Yellow
Initialization 
Green
Standby / Normal Operation
Red
Fault Indication Code
Table 1 
Error 
Code
DGN LED status
Fault Type
1
Red 
Ignition Control Internal Failure
2
2 Red Flashes
Gas Valve Not Connected
3
3 Red Flashes
Ignition/Flame Sense Failure
4
4 Red Flashes
Reset Switch is Shorted
5
Slow Red and Green Flashes
Low Voltage Detection
6
Fast Red and Orange Flashes
Ignition Control is in Reset Delay
TMB2176N
1
Diagnostic (DGN) LED
Figure 5 
1