APC galaxy 9000 User Manual

Page of 40
34006451EN/AC
 - Page 23
Installation
Connection to battery circuit breaker QF1  
Emergency shutdown 
 
2.9 Connections between cubicles
 (modular UPSs or parallel UPSs with SSC)
  
Connections between APOZ boards
   
Connections between rectifier-inverter cubicles  
Connect the cable from connector XR3 (pins 7 to 12) of the rectifier-inverter cubicle remote relay board to connector XR1 of 
the battery cubicle containing battery circuit breaker QF1.
The UPS emergency shutdown function is generally wired to a "mushroom-head" type emergency off button.
Important: 
In the case of a complex installation with a number of units, there should only be one emergency shutdown pushbutton and 
this pushbutton must interrupt all the active conductors of all the units.
For the same reason, it is essential for the pushbutton to open the upstream mains 1, mains 2, and external maintenance 
bypass line protective circuit breakers.
Each type of unit (UPS and Static Switch Cubicle) must have an independent, volt-free contact connected to the emergency 
shutdown pushbutton. This pushbutton must therefore have as many contacts as there are units in the installation, as well as 
the contact or contacts required to open the upstream mains 1 and 2 protective circuit breakers. The emergency shutdown 
pushbutton turns off the rectifier-chargers and inverters and opens the battery circuit breakers. The emergency shutdown 
signal will be cleared when the emergency shutdown pushbutton contact has been reset.
The emergency shutdown pushbutton should not be connected to the Static Switch Cubicle since the pushbutton opens the 
circuit breaker protecting the upstream circuit (mains 2) and the Static Switch Cubicle is therefore no longer powered (invert-
ers off and mains 2 down).
On modular UPSs, interconnections are made on the APOZ (figure 17) and MISI (figures 19 to 21) boards in the UPS cubicles 
(see the layout of the boards in the figures in the previous section).
For parallel UPSs with a centralised SSC, interconnections are made on the APOZ boards in the UPS cubicles (figure 17) 
and the ACPZ boards (see the layout of the boards in the figures in the previous section) in the SSC (figure 18).
– these connections are made using the ribbon cables supplied;
– the purpose of the connection is to make a loop: connector XM137 of the APOZ board of one UPS being connected to 
connector XM136 of the APOZ board of the next UPS and so on until the first board is returned to.
Important
Outside the cubicles, group the APOZ inter-board and ACPZ or MISI inter-board connections with the inter-cubicle auxiliary 
connections, and separate this assembly from the power cables.
Fig. 17
APOZ board
rectifier-inverter 1
APOZ board
rectifier-inverter 2
APOZ board
rectifier-inverter 3
ribbon cables supplied
XM137
XM136
XM137
XM136
XM137
XM136