ACS 255 User Manual

Page of 63
Problem  
Possible cause  
Corrective action 
Nothing displays when the 
controller is turned on. 
The internal mechanism is 
not inserted properly into the 
housing. 
Properly insert the internal 
mechanism into the housing. 
The power supply is not 
connected to its terminals 
properly. 
Properly connect the power 
supply to the power supply 
terminals. 
No power is supplied, or the 
supplied power is not within 
the specified range. 
Supply a voltage of 85 to 125 
VAC to the power supply 
terminals of the controller. 
Disconnect switch or Control 
Power switch not set to ON
Control Power fuse blown. 
Check control power fuse for 
continuity. Turn disconnect 
switch and control power 
switch ON
Process value is abnormal or 
not obtained. 
Input polarity on thermo-
couple is wrong or 
connection is wrong. 
Properly wire the terminals. 
No compensating lead wires 
used for extension of the 
thermocouple. 
Use proper compensating 
lead wires and terminals. 
Thermocouple and controller 
are connected by wires other 
than proper lead wires. 
Use a dedicated thermo-
couple connector. If a 
connector is a metal different 
from the thermocouple and 
controller, a temperature 
error may result. 
Sensor is broken or short-
circuited. 
Replace with a good sensor. 
The controller is influenced 
by noise or other induction. 
Separate input wires as far 
as possible from the origin of 
the noise. 
Celsius temperatures used 
instead of Fahrenheit or vice 
versa. 
Setup mode level 2 display  
d-U. S-V display shows 
setting. 
 
Determining Temperature Controller Errors or Sensor Errors 
 
Using a Thermocouple 
 
If the controller displays a temperature that is close to room temperature (70ºF/21ºC) when you short-
circuit controller input terminals, the controller is normal and the sensor is probably broken, short-
circuited, or incorrectly wired. 
Using a Platinum Resistance Thermometer 
 
If the controller displays a temperature of about 0.0°C (32ºF) when you insert a 100-ohm resistor between 
terminals A and –B of the controller, and you short-circuit controller terminals +B and  
–B, the controller is normal and the sensor is probably broken, short-circuited, or incorrectly wired.
 
 
Troubleshooting 