Siemens bacnet 125-5037 User Manual

Page of 48
Point Database 
24 
 
Siemens Building Technologies, Inc. 
Descriptor Address
Application Description 
DO 4 
{44} 
All except 
2562, 2564,  2566 
Digital output 4 controls a 24 Vac load with an ON 
or OFF status. If Motor 2 is enabled, DO 4 is 
coupled with DO 3 to control an actuator. 
HEAT STAGE 2 
{44} 
2562, 2564,  2566 
This point is DO 4 in applications with electric 
reheat. This digital output controls the contact for 
the second stage of heating and has a status of ON 
or OFF. 
DO 5 
{45} 
2560, 2561,  2563, 
2597  
Digital output 5 controls a 24 Vac load with an ON 
or OFF status. If Motor 3 is enabled, DO 5 is 
coupled with DO 6 to control an actuator. 
DO 5 
{45} 
2565, 2567 
Digital output 5 controls a 24 Vac load with an ON 
or OFF status. 
HEAT STAGE 3 
{45}
2562, 2564,  2566 
This point is a digital output used to control the 
contact for the third stage of heating and has a 
status of ON or OFF. 
DO 6 
{46} 
All except  
2564, 2565,  2566, 
2567  
Digital output 6 controls a 24 Vac load with an ON 
or OFF status. If Motor 3 is enabled, DO 6 is 
coupled with DO 5 to control an actuator.  
In applications with CAL MODULE set to YES, this 
digital output controls the Autozero Module to 
calibrate the controller's internal air velocity 
transducer. 
FAN 
{46} 
2564, 2565,  2566, 
2567  
This point is a digital output used to control the fan. 
ON indicates that the DO is energized; OFF 
indicates that the DO is de-energized. 
DMPR COMD 
{48} 
All except 2597  
The value to which the damper motor is 
commanded in percent of full travel. 
MTR1 COMD 
{48} 
2597  
The value to which the Motor 1 actuator is 
commanded in percent of full travel. 
DMPR POS 
{49} 
All except 2597  
The current position of the damper motor in percent 
of full travel. This value is calculated based on 
motor run time. 
MTR1 POS 
{49} 
2597 
The current position of Motor 1  in percent of full 
travel. This value is calculated based on motor run 
time. See MTR1 TIMING. 
MTR1 TIMING 
51 
All 
The time required for the Motor 1 actuator to travel 
from full closed to the full open position. 
MTR2 COMD 
{52}
2560, 2561,  2597 
The value to which the Motor 2 actuator is 
commanded in percent of full travel (for use as an 
auxiliary slave point). 
VLV COMD 
{52} 
 
2565, 2567  
The value to which the valve actuator is 
commanded in percent of full travel for applications 
using a water valve. 
VLV1 COMD 
{52} 
2563 
The value to which the valve 1 actuator is 
commanded in percent of full travel for applications 
using a water valve.