MGE UPS Systems 3000 User Manual
MGE UPS SYSTEMS
Addenda du manuel d’installation
5103056000_AB
Addenda du manuel d’installation
5103056000_AB
4
4- Maximum power allowed in parallel mode :
4-1 Without external by-pass cubicle :
4-1 Without external by-pass cubicle :
= 1 x Pn
+
= 1 x Pn
4-2 With external by-pass cubicle :
+
= 2 x Pn
+
+
= 3 x Pn
+
+
+
= 3 x Pn
Maximum power allowed with 4 UPS in parallel is 3 x Pn
5/ Parallel mode restrictions:
G3000 single unit
G3000 parallel system
EMC Level
Class B
Class A
ECO mode
Yes No
Frequency converter
Yes No
Synchronisation module
compatibility
compatibility
No No
Remote Power Off function
through SolutionPac / Wan
or AS4i (*)
through SolutionPac / Wan
or AS4i (*)
Yes with UPS NT>10
No
Operating system shut down
and UPS shut off through
MGE communication
products (*)
and UPS shut off through
MGE communication
products (*)
Yes with UPS NT>10
No
Schedule UPS and systems
on/off through PSP or
SolutionPac / Wan (*)
on/off through PSP or
SolutionPac / Wan (*)
Yes with UPS NT>10
No
(*) with the exception of G 3000 operating under eco mode or by-pass mode