MGE UPS Systems 3000 User Manual

Page of 8
MGE UPS SYSTEMS 
Addenda du manuel d’installation 
5103056000_AB 
4
4- Maximum power allowed in parallel mode : 
 
 
4-1 Without external by-pass cubicle : 
 
 
 
 
 
= 1 x Pn 
 
 
 
 
      
+
   
 
= 1 x Pn 
 
 
 
 
4-2 With external by-pass cubicle : 
 
 
 
 
 
 
      
+
   
 
= 2 x Pn 
 
 
 
 
 
 
 
 
 
     +   
      +   
 
= 3 x Pn  
 
 
 
 
 
      +   
       +   
          +              
  = 3 x Pn  
 
 
 
 
Maximum power allowed with 4 UPS in parallel is 3 x Pn  
 
5/ Parallel mode restrictions: 
 
 
 
G3000 single unit 
G3000 parallel system 
EMC Level 
 Class B 
Class A 
ECO mode 
Yes No 
Frequency converter 
Yes No 
Synchronisation module 
compatibility 
No No 
Remote Power Off function 
through SolutionPac / Wan 
or AS4i (*) 
Yes with UPS NT>10 
No 
Operating system shut down 
and UPS shut off through 
MGE communication 
products (*) 
Yes with UPS NT>10 
 
No 
Schedule UPS and systems 
on/off through PSP or 
SolutionPac / Wan (*) 
Yes with UPS NT>10 
 
No 
 
 (*) with the exception of G 3000 operating under eco mode or by-pass mode