heatcraft-refrigeration-p h-im-77d User Manual

Page of 16
12
Wall Mount Back Bar Unit Cooler
Dimensional Diagram
Mounting
The.Wall.Mount.Back.Bar.Unit.Cooler.is.a.low.height.unit.designed.for.undercounter.applications..Air.is.drawn.in.at.the.bottom.
of.the.unit.and.discharged.out.the.front..Two.mounting.angles.are.included.with.the.unit.and.should.be.installed.to.space.the.
unit.3/4”.off.the.wall..Air.deflector(s).are.included.and.can.be.mounted.over.the.top.half.of.the.fan.guard.to.direct.the.air.up..
The.deflector.may.be.left.off.if.total.horizontal.air.movement.is.desired..If.used,.the.deflector.can.be.field.formed.to.direct.the.
air.where.needed..Locating.holes.and.screws.are.provided.
Dimensional Data
 
 
                
 
 
 
 
 
 
 
 
 
Approx.
 Model 
BTUH  
               Motor Data 
 
                 Dimensions (In.) 
 
 
Ship Wt.
    BB 
10°F TD 
CFM 
Qty. 
HP 
(Lbs.)
  L10 
1,000 
90 
1/150 
19
/
4
 
19
1
/
8
 
18 
17
1
/
2
 
7
1
/
16
 
16
5
/
8
 
17
  M11 
1,100 
90 
1/150 
19
/
4
 
19
1
/
8
 
18 
17
1
/
2
 
7
1
/
16
 
16
5
/
16
  L15 
1,500 
180 
1/150 
26
1
/
4
 
25
5
/
8
 
24
1
/
2
 
24 
4
1
/
16
 
8
5
/
8
 
2
1
/
8
 
20
  M16 
1,600 
180 
1/150 
26
1
/
4
 
25
5
/
8
 
24
1
/
2
 
24 
4
1
/
16
 
8
5
/
8
 
2
1
/
8
 
19
 Low 
 
-10°F Sat. Suction Temp.   
 
-15°F Sat. Suction Temp.   
 
Temp 
BTUH @                         R-404A 
 
BTUH @                        R-404A 
 
Model  10°F TD 
Alco 
Sporlan 
15°F TD 
Alco 
Sporlan 
BBL10 
1000 
HFS-1/8SZ 
EFS-1/8Z
 
1500 
HFS-1/8SZ 
EFS-1/8Z 
BBL15 
1500 
 
 
2250 
HFS-1/4SZ 
EFS-1/6Z 
 
 
 
 
 
 
 
 Med 
  25°F Sat. Suction Temp. 
 
  20°F Sat. Suction Temp.   
 
Temp 
BTUH @                        R-22 
 
BTUH @                        R-22 
 
Model  10°F TD 
Alco 
Sporlan 
15°F TD 
Alco 
Sporlan 
BBM11 
1100 
HFS-1/4HC 
EFV-1/5C
 
1870 
HFS-1/4HC 
EFV-1/5C
 
BBM16 
1600 
 
 
2720 
 
 
 
 
 
 
 
 
 
Expansion Valve Recommendations
  Description 
All Sizes Part No.
  115V Motor 
2500701
  208/20V Motor 
2500801
  Fan Blade 
5101B
  Fan Guard 
5054D
  Motor Mount 
91179001
NOMENCLATURE
BB  L  S 10  A  G
A = 115-1-60
B = 208/20-1-60
Revision
Back Bar Unit Cooler
L = Low Temp Unit
M = Med. Temp Unit
Size
Blank = Std. Unit
S = Slave Unit
M = Master Unit
FOR FOOD 
SERVICE 
INSTALLATIONS
. . .  seal any joint 
between unit cooler and 
cooler liner with a sealant 
listed by the National 
Sanitation Foundation, 
Standard 51
NOTE:  All units have /8 O.D. suction, 1/2 O.D. sweat inlet connection and 1/2 O.D. drain.
Commercial Refrigeration Parts
Replacement Parts