T7147 REMOTE SENSOR AND OVERRIDE MODULE
63-4065—1
4
WIRING
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can 
introduce disruptive electrical interference (noise).
Keep wiring at least one foot away from large inductive 
loads such as motors line starters, lighting ballasts, 
and large power distribution panels.
Shielded cable is required in installations where these 
guidelines cannot be met.
Ground shield only to grounded controller case.
IMPORTANT
All wiring must comply with local codes and 
ordinances.
NOTES:
Terminal screws are provided on the device for 
wiring connections.
Wiring to device is low voltage and need not be 
in conduit unless required by code.
1.
Connect correct control wires from the Q7300 subbase 
to the T7147 (see Fig. 4 and 5).
2.
Ensure that Q7300 subbase switch 5 (local/remote 
sensor select switch) is in the OFF position. (Refer to 
the T7300/Q7300 Specification sheet, form 63-4038, 
for details).
IMPORTANT
The ground (GND) connection at the T7147 is 
required. Use the junction box or conduit for a 
convenient grounding location.
3.
Ensure all connections are tight and secure. Loose or 
intermittent wire connections cause inconsistent system 
operation.
4.
When installation is complete, perform the checkout 
procedure (see the Checkout section).
Averaging Sensors
When the controlled zone is a large area, it can be 
advantageous to use a T7147 and several remote 
temperature sensors dispersed throughout the area to obtain 
an average zone temperature signal. (See Fig. 6 and 7.)
NOTE:
Only one T7147 can be used in any one 
T7300/Q7300 system.
Fig. 4. Connecting wires to T7147.
T
T
CA5
CA4
CA3
CA2
CA1
GND
CONNECTIONS TO CA3 AND CA4 NOT REQUIRED 
ON T7147A2000.
ROUTE EXCESS WIRING AWAY FROM SENSOR 
ELEMENT FOR OPTIMUM PERFORMANCE.
M17880
1
1
2
2
CA5
CA4
CA3
CA2
CA1
GND