Set Up and Calibration Procedures 
Input Set Up Group 
40 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink Prompt 
 
FILTYP 
NONE
  
 
SPIK 
 
S+LP  
 
LPAS  
 
default = LPAS
 
INPUT FILTER TYPE
— Allows the selection of a software 
digital input filter to smooth the input signal.  
Spike
— Selects spike filter to remove transients in the input 
signal when actuator is installed in noisy environments.  
Spike plus Low Pass
— Selects spike and low pass filtering. 
Allows setting of lag time constant for low pass filter. 
Low Pass
— Selects low pass filter.  
Allows setting of lag time constant. 
NOTE:  When Input Type (R_SP or S_90) is selected, Input 
Filter Type = NONE.  
LPFILT * 
0 to 50.00  
(in seconds) 
 
default = 0.5 
LAG TIME CONSTANT
— (Filter Type S+LP or LPAS only) 
Allows you to set the first order lag time constant of the low 
pass filter when selected. Range is from 0 to 50 seconds. 
NOTE:  When Input Type (R_SP or S_90) is selected, Low 
Pass Filter Value is not configurable. 
Direct 
CCW  
CW 
 
 
 
default = CCW  
 
ACTUATOR ROTATION
—This selection determines the 
direction of rotation of the actuator shaft. 
Counterclockwise 
rotation 
 
Clockwise
 rotation 
NOTE:  Actuator rotation is the direction of the output shaft 
when facing the end of the shaft and refers to the direction of 
rotation on increasing signal. 
Dband 
0.2
  to 5.0 
(in percent of 
span) 
default = 0.5
 
INPUT DEADBAND
— Specifies an adjustable gap that is the 
difference between the setpoint value and the value at which 
the motor energizes.  Deadband is set in percent of full span.  
FSFTYPH 
 
 
 
 
 
LAST 
UP 
DOWN 
USER  
 
default = UP 
FAILSAFEHI TYPE
—Selects the motor position you want 
the actuator to go to when input signal is above the high end 
range value. 
NOTE:  Failsafe condition occurs when the input exceeds its 
high end range value by 3%,  
Last Position
—Actuator motor remains at last position. 
Up
—Actuator motor moves to full scale value. 
Down
—Actuator motor moves to zero value. 
User selected value
—Actuator motor moves to a customer-
defined value.   
*  
Allows setting of failsafehi input value. 
 
FsFVALH * 
0
 to 100% 
 
 
default = 100 
FAILSAFEHI INPUT VALUE
—(FailsafeHI Type USER only) 
Selects the motor position you want the actuator to go to 
when input signal is above the high end range value. 
Range is from 0 to 100%.