Equal Percentage Valve Characteristic 
Table 11 contains values that approximate an equal percentage valve characteristic in the actuator.  When 
the EQUL custom characterization type is selected, the values in Table 11 are automatically loaded into the 
actuator configuration to produce the characteristic as presented in the graph. The Xn VAL is the input 
value as a percentage of range and Yn VAL is the characterized output (actuator shaft position) as a 
percentage of range. 
 
Table 11 Equal Percentage Valve Characteristics 
 
Order 
Xn VAL 
% of 
Range 
Yn Val 
% of 
Range 
 
Equal Percentage Valve Characterization 
0 0 0 
1 5 0.8 
2 10 2.1 
3 15 3.2 
4 20 4.9 
5 25 6.5 
6 30 8.4 
7 35 
10.7 
8 40 
13.2 
9 45 
15.7 
10 50 18.7 
11 55 22.6 
12 60 27.2 
13 65 33.4 
14 70 40 
15 75 46 
16 80 53.8 
17 85 63.2 
18 90 73.7 
19 95 86.2 
20 100 100 